Warning – Yokogawa EJX115A User Manual
Page 14
 
<2. Handling Cautions>
12
IM 01C25A01-01E
Transmitter
Supply
Safety Barrier*1
Nonhazardous Location
[Installation Diagram] (for EJX910A and EJX930A)
Hazardous Location
+
–
+
–
F0211.ai
Sensor out
RTD sensor
*2
● Without pulse output
● With pulse output
Transmitter
Supply
Safety Barrier*1
Nonhazardous Location
Hazardous Location
+
–
+
–
+
Sensor out
RTD sensor
*2
Safety Barrier*1
+
–
Pulse
*1: • In any safety barriers used the output current must be
limited by a resistor “R” such that Io=Uz/R.
• The safety barrier shall be certified by notify body EU as
ATEX.
• When using non isolation barrier, connect to IS earthing
system.
*2: • RTD sensor is prepared by the user.
• The sensor signal line must withstand a test voltage of
500 V AC.
WARNING
To	satisfy	IP66	or	IP67,		apply	waterproof	glands	to	the	
electrical	connection	port.
c. ATEX Flameproof Type
Caution for ATEX flameproof type.
Note 1. Model EJX/EJA-E Series pressure transmitters
with	optional	code	/KF22	for	potentially	
explosive	atmospheres:
•	 No.	KEMA	07ATEX0109	X
•	 Applicable	Standard:	EN	60079-0:2009,		
EN 60079-1:2007, EN 60079-31:2009
•	 Type	of	Protection	and	Marking	Code:	
	 Ex	d	IIC	T6...T4	Gb,		Ex	tb		IIIC		T85°C	Db
•	 Group:	II
•	 Category:	2G,	2D
•	 Enclosure:	IP66	/	IP67
•	 Temperature	Class	for	gas-poof:		
T6, T5, and T4
• Ambient Temperature for gas-proof:
–50	to	75°C	(T6),	–50	to	80°C	(T5),	and	
–50	to	75°C	(T4)
• Maximum Process Temperature (Tp.) for gas-
proof:
	 85°C	(T6),	100°C	(T5),	and	120°C	(T4)
•	 Maximum	Surface	Temperature	for	dust-proof:
T85°C (Tamb.: –30* to 75°C, Tp.: 85°C)
* –15°C when /HE is specified.
Note 2. Electrical Data
•	 Supply	voltage:	42	V	dc	max.
•	 Output	signal:	4	to	20	mA
Note 3. Installation
• All wiring shall comply with local installation
requirement.
• The cable entry devices shall be of a certified
flameproof type, suitable for the conditions of use.
Note 4. Operation
• Keep the “WARNING” label attached to the
transmitter.
WARNING: AFTER DE-ENERGIZING, DELAY
5	MINUTES	BEFORE	OPENING.	WHEN	THE	
AMBIENT	TEMP.≥65°C,	USE	HEAT-RESISTING	
CABLE	AND	CABLE	GLAND	≥90°C.
• Take care not to generate mechanical sparking
when	accessing	to	the	instrument	and	peripheral	
devices	in	a	hazardous	location.
Note 5. Special Conditions for Safe Use
WARNING
• Electrostatic charge may cause an exlosion
hazard.		Avoid	any	actions	that	cause	the	
gerenation	of	eletrostatic	charge,	such	as	rubbing	
with	a	dry	cloth	on	coating	face	of	the		product.
• In the case where the enclosure of the Pressure
Transmitter	is	made	of	aluminium,	if	it	is	mounted	
in	an	area	where	the	use	of	category	2D	apparatus	
is	required,	it	shall	be	installed	in	such	a	way	
that	the	risk	from	electrostatic	discharges	and	
propagating	brush	discharges	caused	by	rapid	
flow	of	dust	is	avoided.
• The instrument modification or parts replacement
by	other	than	an	authorized	Representative	of	
Yokogawa	Electric	Corporation	is	prohibited	and	
will	void	the	certification.
• To satisfy IP66 or IP67, apply waterproof glands to
the electrical connection port.