4 mounting the flushing connection ring, Mounting the flushing connection ring, Important – Yokogawa EJX115A User Manual
Page 22
 
<3. Installation>
20
IM 01C25A01-01E
IMPORTANT
The	transmitter	should	be	installed	at	least	600	mm	below	
the	high	pressure	(HP)	process	connection	to	ensure	a	
positive	head	pressure	of	fill	fluid.	Pay	special	attention	to	
vacuum	applications.
If	it	can	not	be	installed	at	least	600	mm	below	the	HP	
process	connection,	please	use	the	equation	below:
h=
× 0.102
[mm]
(P–P0)
ds
h: Vertical height between the HP process connection
and	the	transmitter	(mm)
h≤0:		Install	the	transmitter	at	least	h	(mm)	below	the	
HP process connection
h>0: Install the transmitter at most h (mm) above the
HP process connection
P:	 Pressure	in	the	tank	(Pa	abs)
P0:	Minimum	working	pressure	limit	of	the	transmitter	(Pa	
abs) See below table.
[For fill fluid code A, B, C, D, E]
Wetted parts
material
code
Capillary
length
Process connection size
code
2, 8
3
4,W
SW
1 to 5m
6790
3190
6 to 10m
10030
3520
SE
1 to 5m
6790
3190
6 to 10m
10030
3520
SY
1 to 5m
3190
6 to 10m
3520
HW
1 to 5m
19150
6140
6 to 10m
8290
TW
1 to 5m
9620
3620
6 to 10m
4210
UW
1 to 5m
9540
4750
6 to 10m
6050
[For fill fluid code 1, 2, 4]
Wetted parts
material
code
Capillary
length
Process connection size
code
2, 8
3
4,W
SW
1 to 5m
2570
320
6 to 10m
4680
530
SE
1 to 5m
2570
320
6 to 10m
4680
530
SY
1 to 5m
320
6 to 10m
530
HW
1 to 5m
10220
2050
6 to 10m
3450
TW
1 to 5m
4270
570
6 to 10m
960
ds: Specific gravity of fill fluid (at 25°C). See below table.
Fill fluid
code
A, 1, 4
B
C, 2
D
E
ds: Specific
gravity
1.07
0.94
1.09
1.90 to
1.92
1.09
F0308.ai
P
Low pressure side
High
pressure
side
(+)
(–)
0
h
Figure 3.8
Example of Installation to Tank
(Caution on Installation)
3.4 Mounting the Flushing
Connection Ring
3.4.1 Mounting to Pressure Detector
Section
The	flushing	connection	ring	is	mounted	to	the	pressure	
detector	section	as	shown	in	Figure	3.9.		
At	the	factory	shipment,	the	flushing	connection	ring	is	
already	assembled	and	attached	to	process	detector	
section.
Ring holder
Spiral gasket
F0309.ai
View from pressure
detector section
Groove for
installing
spiral gasket
Pressure-detector section
Drain/vent plug
Ring
Figure 3.9
Mounting to Pressure Detector Section
(1) Mount the ring holder on the ring and loosely tighten
the mounting screws.
(2) Place the spiral gasket in the ring groove. With the
ring	correctly	aligned	and	flush	with	the	face	of	the	
pressure	detector,	securely	tighten	each	ring	holder’s	
mounting	screws.
(3) Position the ring so that the drain/vent plugs are
aligned straight up and down.