2 zero point adjustment, Zero point adjustment, Important – Yokogawa EJX115A User Manual
Page 38
 
<6. Operation>
36
IM 01C25A01-01E
6.2 Zero Point Adjustment
After	completing	preparations	for	operating	the	
transmitter,	adjust	the	zero	point.
Zero	point	adjustment	can	be	done	by	turning	the	
transmitter’s	zero-adjustment	screw	or	by	using	the	
communicator.	This	section	describes	the	procedure	
for	the	zero-adjustment	screw.	For	the	communicator	
procedure,	please	refer	to	manuals	in	the	attached	
CD-ROM.
IMPORTANT
Do	not	turn	off	the	power	to	the	transmitter	
immediately	after	performing	a	zero	point	adjustment.	
Powering	off	within	30	seconds	of	performing	this	
procedure	will	return	the	zero	point	to	its	previous	
setting.
6.2.1 Adjusting Zero Point for Differential
Pressure Transmitters
Before	adjusting	zero	point,	make	sure	that	the	equalizing	
valve	is	open.
Zero-adjustment screw cover
F0603.ai
Figure 6.2
External Zero Adjustment Screw
The	zero-adjustment	screw	is	located	inside	the	cover.	
Use	a	slotted	screwdriver	to	turn	the	zero-adjustment	
screw.	Equalize	the	transmitter,	then	turn	the	screw	
clockwise	to	increase	the	output	or	counterclockwise	to	
decrease	the	output.	The	zero	point	adjustment	can	be	
made	with	a	resolution	of	0.01%	of	the	setting	range.	The	
degree	of	zero	adjustments	varies	with	the	screw	turning	
speed;	turn	the	screw	slowly	to	make	a	fine	adjustment,	
quickly	to	make	a	rough	adjustment.
When	using	differential	pressure	transmitters	for	level	
measurement	and	if	you	cannot	obtain	the	lower	range	
value	from	the	actual	measurement	value	of	0%,	refer	to	
subsection	6.2.2(2).	
6.2.2 Adjusting Zero Point for Gauge/
Absolute Pressure Transmitters
(1) When you can obtain the Low Range Value
from the actual measured value of 0%
(0 kPa, atmospheric pressure);
For	pressure	measurement	using	gauge	pressure	
transmitters,	follow	the	steps	below	before	performing	
zero	point	adjustment.
1)	 Close	the	tap	valve	(main	valve).
2)	 Loosen	the	fill	plug	so	that	the	pressure	applied	to	the	
transmitter is only the head of the seal liquid.
3)	 Adjust	the	zero	point	at	this	status.
4)	 After	the	adjustment,	close	the	fill	plug	and	then	
gradually open the tap valve.
Use	a	slotted	screwdriver	to	turn	the	zero-adjustment	
screw.	Turn	the	screw	clockwise	to	increase	the	output	or	
counterclockwise	to	decrease	the	output.	The	zero	point	
adjustment	can	be	made	with	a	resolution	of	0.01%	of	the	
setting	range.	Since	the	degree	of	the	zero	adjustment	
varies	with	the	screw	turning	speed,	turn	the	screw	slowly	
to	make	a	fine	adjustment	and	quickly	to	make	a	rough	
adjustment.
(2) When you cannot obtain the Low Range
Value from the actual measured value of
0%;
Adjust	the	transmitter	output	to	the	actual	measured	
value	obtained	by	a	digital	manometer	or	a	glass	gauge.
[Example]	
The	measuring	range	of	50	to	250	kPa;	the	actual	
measured	value	of	130	kPa.	
130–50
250–50
Actual measured value=
x100=40.0%
(=10.4mA)
Turn	the	screw	to	match	the	output	signal	to	the	actual	
measured	value.