IMPORTANT
For	combined	approval	types
Once	a	device	of	multiple	approval	type	is	installed,	
it	should	not	be	re-installed	using	any	other	approval	
types.	Apply	a	permanent	mark	in	the	check	box	of	
the	selected	approval	type	on	the	certification	label	on	
the	transmitter	to	distinguish	it	from	unused	approval	
types.
2.4.1 FM Approval
a. FM Intrinsically Safe Type
Caution	for	FM	intrinsically	safe	type.	(Following	
contents	refer	“DOC.	No.	IFM022-A12”)
Note 1. Model EJX/EJA-E Series Differential, gauge
and	absolute	pressure	transmitters	with	optional	
code	/FS1	are	applicable	for	use	in	hazardous	
locations.
• Applicable Standard: FM3600, FM3610, FM3611,
FM3810
• Intrinsically Safe for Class I, Division 1, Groups A,
B,	C	&	D.	Class	II,	Division	1,	Groups	E,	F	&	G	and	
Class	III,	Division	1,	Class	I,	Zone	0	in	Hazardous	
Locations,	AEx	ia	IIC
• Nonincendive for Class I, Division 2, Groups
A,	B,	C	&	D.	Class	II,	Division	2,	Groups	F	&	G	
and	Class	I,	Zone	2,	Groups	IIC,	in	Hazardous	
Locations.
•	 Outdoor	hazardous	locations:	NEMA	TYPE	4X
•	 Temperature	Class:	T4
•	 Ambient	temperature:	–60	to	60°C
Note 2. Entity Parameters
•	 Intrinsically	Safe	Apparatus	Parameters
	 [Groups	A,	B,	C,	D,	E,	F	and	G]	
Vmax = 30 V
Ci = 6 nF
Imax = 200 mA
Li = 0 µH
Pmax = 1 W
*	 Associated	Apparatus	Parameters
	 (FM	approved	barriers)
Voc ≤ 30 V
Ca > 6 nF
Isc ≤ 200 mA
La > 0 µH
Pmax ≤ 1W
•	 Intrinsically	Safe	Apparatus	Parameters
	 [Groups	C,	D,	E,	F	and	G]
Vmax = 30 V
Ci = 6 nF
Imax = 225 mA
Li = 0 µH
Pmax = 1 W
*	 Associated	Apparatus	Parameters
	 (FM	approved	barriers)
Voc ≤ 30 V
Ca > 6 nF
Isc ≤ 225 mA
La > 0 µH
Pmax ≤ 1 W
•	 Entity	Installation	Requirements
	 Vmax	≥	Voc	or	Uo	or	Vt,	Imax	≥	Isc	or	Io	or	It,	
	 Pmax	(or	Po)	≤	Pi,	Ca	or	Co	≥	Ci	+	Ccable,
	 La	or	Lo	≥	Li	+	Lcable
Note 3. Installation
• Barrier must be installed in an enclosure that
meets the requirements of ANSI/ISA S82.01.
• Control equipment connected to barrier must not
use or generate more than 250 V rms or V dc.
• Installation should be in accordance with ANSI/ISA
RP12.6	“Installation	of	Intrinsically	Safe	Systems	
for	Hazardous	(Classified)	Locations”	and	the	
National	Electric	Code	(ANSI/NFPA	70).
• The configuration of associated apparatus must be
FMRC Approved.
• Dust-tight conduit seal must be used when
installed	in	a	Class	II,	III,	Group	E,	F	and	G	
environments.
• Associated apparatus manufacturer’s installation
drawing	must	be	followed	when	installing	this	
apparatus.
• The maximum power delivered from the barrier
must not exceed 1 W.
• Note a warning label worded “SUBSTITUTION
OF	COMPONENTS	MAY	IMPAIR	INTRINSIC	
SAFETY,”	and	“INSTALL	IN	ACCORDANCE	WITH	
DOC.	No.	IFM022-A12”
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by	other	than	authorized	representative	of	
Yokogawa	Electric	Corporation	is	prohibited	and	
will	void	Factory	Mutual	Intrinsically	safe	and	
Nonincendive	Approval.
F0204.ai
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
Class 1, Zone 0 in
Hazardous (Classified)
Locations AEx ia IIC
Pressure Transmitters
Safety Barrier
Supply
Hazardous Location
Nonhazardous Location
General
Purpose
Equipment
+ 
– 
+ 
– 
+ 
– 
+ 
– 
[Intrinsically Safe]
H
an
dlin
g C
au
tio
ns
2