Warning – Yokogawa EJX115A User Manual
Page 13
 
<2. Handling Cautions>
11
IM 01C25A01-01E
WARNING
• In the case where the enclosure of the Pressure
Transmitter	is	made	of	aluminium,	if	it	is	mounted	
in	an	area	where	the	use	of	category	1	G	
apparatus	is	required,	it	must	be	installed	such,	
that,	even	in	the	event	of	rare	incidents,	ignition	
sources	due	to	impact	and	friction	sparks	are	
excluded.
• Electrostatic charge may cause an exlosion
hazard.		Avoid	any	actions	that	cause	the	
gerenation	of	eletrostatic	charge,	such	as	rubbing	
with	a	dry	cloth	on	coating	face	of	the	product.
• In case of the enclosure of the Pressure
Transmitter	with	paint	layers,	if	it	is	mounted	in	an	
area	where	the	use	of	category	2D	apparatus	is	
required,	it	shall	be	installed	in	such	a	way	that	the	
risk	from	electrostatic	discharges	and	propagating	
brush	discharges	caused	by	rapid	flow	of	dust	is	
avoided.
• To satisfy IP66 or IP67, apply waterproof glands to
the electrical connection port.
• When the lightning protector option is specified,
the	apparatus	is	not	capable	of	withstanding	the	
500V	insulation	test	required	by	EN60079-11.	This	
must	be	taken	into	account	when	installing	the	
apparatus.
b. ATEX Intrinsically Safe Type for EJX910A
and EJX930A
Caution for ATEX Intrinsically safe type.
Note 1. Model EJX Series pressure transmitters with
optional	code	/KS2	for	potentially	explosive	
atmospheres:
• No. KEMA 06ATEX 0037X
• Applicable Standard:
EN 50014:1997, EN 50020:2002,
EN 50284:1999, EN 50281-1-1:1998
• Type of Protection and Marking code:
EEx ia IIC T4
• Group: II
• Category: 1G, 1D
• Ambient Temperature for gas-proof:
–50* to 60°C
* –15°C when /HE is specified.
• Process Temperature (Tp.): 120°C max.
• Maximum Surface Temperature for dust-proof:
T85°C (Tamb.: –40* to 60°C, Tp.: 80°C)
T100°C (Tamb.: –40* to 60°C, Tp.: 100°C)
T120°C (Tamb.: –40* to 60°C, Tp.: 120°C)
* –15°C when /HE is specified.
• Enclosure: IP66 and IP67
Note 2. Electrical Data
[Supply/Output	circuit	(terminals	+	and	-)]
	 In	type	of	explosion	protection	intrinsic	safety	EEx	
ia	IIC,	only	for	connection	to	a	certified	intrinsically	
safe	circuit	with	following	maximum	values:	
Ui	=	30	V	
Ii	=	200	mA	
Pi	=	0.9	W
	 Effective	internal	capacitance;	Ci	=	10	nF
	 Effective	internal	inductance;	Li	=	0	mH
[Pulse	Output	circuit	(terminals	-	and	pulse)]
	 In	type	of	explosion	protection	intrinsic	safety	EEx	
ia	IIC,	only	for	connection	to	a	certified	intrinsically	
safe	circuit	with	following	maximum	values:	
Ui	=	30	V
	 Ii	=	200	mA
	 Pi	=	0.9	W
	 Ci	=	10	nF
	 Li	=	0	mH
[External	temperature	input	circuit	(connector)]
	 In	type	of	explosion	protection	intrinsic	safety	EEx	
ia	IIC,	with	following	maximum	values:	
Uo	=	30	V
Io = 95.4 mA
Po= 468 mW
	 Co	=	11	nF
	 Lo=	3.9	mH
Note 3. Installation
• All wiring shall comply with local installation
requirements. (Refer to the installation diagram)
• When the analog and pulse circuits are connected
to	separate	barriers,	it	shall	be	assured	that	the	
voltage	difference	between	these	output	circuits	is	
not	more	than	30	V.
• When used in a potentially explosive atmosphere,
Requiring	the	use	of	apparatus	of	equipment	
category	1D	or	2D,	certified	cable	entry	devices	
shall	be	used	that	are	suitable	for	the	application	
and	correctly	installed.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by	other	than	authorized	representative	of	
Yokogawa	Electric	Corporation	is	prohibited	and	
will	void	KEMA	Intrinsically	safe	Certification.
Note 5. Special Conditions for Safe Use
• In the case where the enclosure of the Pressure
Transmitter	is	made	of	aluminium,	if	it	is	mounted	
in	an	area	where	the	use	of	category	1	G	
apparatus	is	required,	it	must	be	installed	such,	
that,	even	in	the	event	of	rare	incidents,	ignition	
sources	due	to	impact	and	friction	sparks	are	
excluded.