5 emc conformity standards, Emc conformity standards, Caution – Yokogawa EJX115A User Manual
Page 17
 
<2. Handling Cautions>
15
IM 01C25A01-01E
• Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature: –50 to 60°C
• Max. Process Temp.: 120°C
• Enclosure: IP66/IP67
Note 2. Entity Parameters
• Intrinsically safe ratings are as follows:
Maximum Input Voltage (Vmax/Ui) = 30 V
Maximum Input Current (Imax/Ii) = 200 mA
Maximum Input Power (Pmax/Pi) = 0.9 W
Maximum Internal Capacitance (Ci) = 10 nF
Maximum Internal Inductance (Li) = 0 µH
• Type "n" ratings are as follows:
Maximum Input Voltage (Vmax/Ui) = 30 V
Maximum Internal Capacitance (Ci) = 10 nF
Maximum Internal Inductance (Li) = 0 µH
• Installation Requirements
Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
Co ≥ Ci + Ccable, Lo ≥ Li + Lcable
Voc ≤ Vmax, Isc ≤ Imax,
Ca ≥ Ci + Ccable, La ≥ Li + Lcable
Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
parameters of barrier.
Note 3. Installation
• In any safety barrier used output current must be
limited by a resistor 'R' such that Io=Uo/R.
• The safety barrier must be IECEx certified.
• Input voltage of the safety barrier must be less
than 250 Vrms/Vdc.
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation and will void IECEx
Intrinsically safe and type n certification.
F0216.ai
EJX Series Pressure
Transmitters
IECEx certified
Safety Barrier
Supply
Hazardous Location
Nonhazardous Location
General
Purpose
Equipment
+ 
– 
+ 
– 
+ 
– 
+ 
– 
[Intrinsically Safe]
Group IIC, Zone 0
F0217.ai
EJX Series Pressure
Transmitters
Supply
Hazardous Location
Nonhazardous Location
+ 
– 
+ 
– 
Not Use
Safety Barrier
[type n]
IECEx Certified
Equipment [nL]
EJX Series Pressure
Transmitters
Group IIC, Zone 2
b. IECEx Flameproof Type
Caution for IECEx flameproof type.
Note 1. Model EJX/EJA-E Series pressure transmitters
with	optional	code	/SF2	or	/SU2	are	applicable	
for	use	in	hazardous	locations:
•	 No.	IECEx	CSA	07.0008
•	 Applicable	Standard:	IEC60079-0:2004,		
IEC60079-1:2003
•	 Flameproof	for	Zone	1,	Ex	d	IIC	T6...T4
•	 Enclosure:	IP66/IP67
•	 Maximum	Process	Temperature:	120°C	(T4),	
100°C (T5), 85°C (T6)
• Ambient Temperature: –50 to 75°C (T4),
–50 to 80°C (T5), –50 to 75°C (T6)
•	 Supply	Voltage:		42	V	dc	max.
•	 Output	Signal:	4	to	20	mA	dc
Note 2. Wiring
• In hazardous locations, the cable entry devices
shall	be	of	a	certified	flameproof	type,	suitable	for	
the	conditions	of	use	and	correctly	installed.	
• Unused apertures shall be closed with suitable
flameproof certified blanking elements.
Note 3. Operation
• WARNING:
AFTER	DE-ENERGIZING,	DELAY	5	MINUTES	
BEFORE	OPENING.	
•	 WARNING:	
	 WHEN	AMBIENT	TEMPERATURE	≥	65°C,		USE	
THE HEAT-RESISTING CABLES ≥ 90°C.
• Take care not to generate mechanical sparking
when	accessing	to	the	instrument	and	peripheral	
devices	in	a	hazardous	location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by	other	than	authorized	representative	of	
Yokogawa	Electric	Corporation	is	prohibited	and	
will	void	IECEx	Certification.
2.5 EMC Conformity Standards
EN61326-1	Class	A,	Table	2	(for	use	in	industrial	
locations)	
EN61326-2-3
CAUTION
To	meet	EMC	regulations,	Yokogawa	recommends	
that	customers	run	signal	wiring	through	metal	
conduits	or	use	shielded	twisted-pair	cabling	when	
installing	EJX/EJA-E	Series	transmitters	in	a	plant.