1 model and specifications check, 2 selecting the installation location, 3 pressure connection – Yokogawa EJX115A User Manual
Page 8: Model and specifications check, Selecting the installation location, Pressure connection, Installation of an explosion-protected instrument, 3 pressure connection warning, Caution, Warning
 
<2. Handling Cautions>
6
IM 01C25A01-01E
2.1 Model and Specifications
Check
The	model	name	and	specifications	are	indicated	on	the	
name	plate	attached	to	the	case.
F0203.ai
Figure 2.2 Name Plate
2.2 Selecting the Installation
Location
The	transmitter	is	designed	to	withstand	severe	
environmental	conditions.	However,	to	ensure	that	it	will	
provide	years	of	stable	and	accurate	performance,	take	
the	following	precautions	when	selecting	the	installation	
location.
(a)		Ambient	Temperature
Avoid	locations	subject	to	wide	temperature	variations	
or	a	significant	temperature	gradient.	If	the	location	is	
exposed	to	radiant	heat	from	plant	equipment,	provide	
adequate	thermal	insulation	and/or	ventilation.
(b)		Ambient	Atmosphere
	 Do	not	install	the	transmitter	in	a	corrosive	
atmosphere.	If	this	cannot	be	avoided,	there	must	be	
adequate	ventilation	as	well	as	measures	to	prevent	
the	leaking	of	rain	water	and	the	presence	of	standing	
water	in	the	conduits.
(c)		Shock	and	Vibration
	 Although	the	transmitter	is	designed	to	be	relatively	
resistant	to	shock	and	vibration,	an	installation	site	
should	be	selected	where	this	is	kept	to	a	minimum.
(d)		Installation	of	Explosion-protected	Transmitters
	 An	explosion-protected	transmitters	is	certified	for	
installation	in	a	hazardous	area	containing	specific	
gas	types.		See	subsection	2.4	“Installation	of	an	
Explosion-Protected	Instrument.”
2.3 Pressure Connection
WARNING
• Never loosen the process connector bolts when an
instrument	is	installed	in	a	process.		The	device	is	
under	pressure,	and	a	loss	of	seal	can	result	in	a	
sudden	and	uncontrolled	release	of	process	fluid.
• When draining toxic process fluids that have
condensed	inside	the	pressure	detector,	take	
appropriate	steps	to	prevent	the	contact	of	such	
fluids	with	the	skin	or	eyes	and	the	inhalation	of	
vapors	from	these	fluids.
The	following	precautions	must	be	observed	in	order	to	
safely	operate	the	transmitter	under	pressure.
(a) Make sure that the process connector bolts are
tightened firmly.
(b) Make sure that there are no leaks in the impulse
piping.
(c) Never apply a pressure higher than the specified
maximum working pressure.
2.4 Installation of an Explosion-
Protected Instrument
NOTE
For F
oundation
Fieldbus and PROFIBUS PA explosion
protected	type,	please	refer	to	manual	in	the	attached	
CD-ROM.
If	a	customer	makes	a	repair	or	modification	to	an	
intrinsically	safe	or	explosionproof	instrument	and	the	
instrument	is	not	restored	to	its	original	condition,	its	
intrinsically	safe	or	explosionproof	construction	may	be	
compromised	and	the	instrument	may	be	hazardous	to	
operate.	Please	contact	Yokogawa	before	making	any	
repair	or	modification	to	an	instrument.
CAUTION
This	instrument	has	been	tested	and	certified	as	
being	intrinsically	safe	or	explosionproof.	Please	
note	that	severe	restrictions	apply	to	this	instrument’s	
construction,	installation,	external	wiring,	maintenance	
and	repair.	A	failure	to	abide	by	these	restrictions	could	
make	the	instrument	a	hazard	to	operate.
WARNING
Maintaining	the	safety	of	explosionproof	equipment	
requires	great	care	during	mounting,	wiring,	and	
piping.	Safety	requirements	also	place	restrictions	on	
maintenance	and	repair.	Please	read	the	following	
sections	very	carefully.
WARNING
The	range	setting	switch	must	not	be	used	in	a	
hazardous	area.