<5. Wiring>
31
IM 01C25A01-01E
5.3.2 Wiring Installation
(1) General-use Type and Intrinsically Safe
Type
With	the	cable	wiring,	use	a	metallic	conduit	or	waterproof	
glands.
• Apply a non-hardening sealant to the terminal box
connection	port	and	to	the	threads	on	the	flexible	
metal	conduit	for	waterproofing.
F0511.ai
Flexible metal conduit
Wiring metal
conduit
Tee
Drain plug
Apply a non-hardening
sealant to the threads for
waterproofing.
Figure 5.10 Typical Wiring Using Flexible Metal
Conduit
(2) Flameproof Type
Wire	cables	through	a	flameproof	packing	adapter,	or	use	
a	flameproof	metal	conduit.
Wiring cable through flameproof packing adapter.
• Apply a non-hardening sealant to the terminal box
connection	port	and	to	the	threads	on	the	flameproof	
packing	adapter	for	waterproofing.
Flameproof packing
adapter
Flexible metal conduit
Wiring metal
conduit
Tee
Drain plug
Apply a non-hardening
sealant to the threads for
waterproofing.
F0512.ai
Figure 5.11 Typical Cable Wiring Using Flameproof
Packing Adapter
Flameproof metal conduit wiring
• A seal fitting must be installed near the terminal box
connection port for a sealed construction.
• Apply a non-hardening sealant to the threads of the
terminal	box	connection	port,	flexible	metal	conduit	
and	seal	fitting	for	waterproofing.
F0513.ai
Non-hazardous area
Hazardous area
Flameproof
heavy-gauge
steel conduit
Tee
Drain plug
Seal fitting
Gas sealing device
Flameproof flexible
metal conduit
Apply a non-hardening
sealant to the threads of
these fittings for
waterproofing
After wiring, impregnate the fitting
with a compound to seal tubing.
Figure 5.12 Typical Wiring Using Flameproof Metal
Conduit
5.4 RTD Cable Connection
(EJX910A/EJX930A)
Connection	of	the	RTD	cable	is	always	required	to	
measure	external	temperature.	Follow	the	procedures	
below	to	connect	a	cable	when	a	cable	gland	or	a	conduit	
is	used.
5.4.1 Connecting Shielded Cable with
Cable Gland (External temperature
input code: -1, -2, -3, and -4)
• RTD connection components: EJX multivariable
transmitter,	two	cable	glands,	and	RTD	cable.	
Two	cable	glands	are	attached.
Transmitter
Cable gland
Electrical connection
RTD cable
with connector
Detail of connector
F0514.ai
Y
L
P
P
U
S
ESL
UP
K
C
E
H
C
M
R
A
L
A
• Magnified view of the RTD connector in the
transmitter's terminal box.
SUPPL
Y
PULSE
CHECK
ALARM
SUPPL
Y
PULSE
CHECK
ALARM
Protection Cap
Connecting Port
F0515.ai
The	RTD	cable	connecting	port	is	covered	with	a	cap	to	
keep	out	dust.	The	cap	should	not	be	removed	until	you	
are	ready	to	install	the	cable.