Wiring, 1 wiring precautions, 2 connections of external wiring to terminal box – Yokogawa EJX115A User Manual
Page 30: Wiring precautions, Connections of external wiring to terminal box, 1 wiring precautions important, 1 power supply wiring connection, 2 configuration tool connection, 3 status output connection
 
<5. Wiring>
28
IM 01C25A01-01E
5. Wiring
NOTE
For F
OUNDATION
Fieldbus and PROFIBUS PA
communication	types,	please	refer	to	manuals	in	the	
attached	CD-ROM.
5.1 Wiring Precautions
IMPORTANT
• Lay wiring as far as possible from electrical noise
sources	such	as	large	capacity	transformers,	
motors,	and	power	supplies.
• Remove electrical connection dust cap before
wiring.
• All threaded parts must be treated with
waterproofing	sealant.	(A	non-hardening	silicone	
group	sealant	is	recommended.)
• To prevent noise pickup, do not pass signal and
power cables through the same ducts.
• Explosion-protected instruments must be wired
in	accordance	with	specific	requirements	(and,	
in	certain	countries,	legal	regulations)	in	order	
to	preserve	the	effectiveness	of	their	explosion-
protected	features.
• The terminal box cover is locked by an Allen head
bolt	(a	shrouding	bolt)	on	ATEX	flameproof	type	
transmitters.	When	the	shrouding	bolt	is	driven	
clockwise	using	an	Allen	wrench,	it	gose	in.	The	
cover	lock	can	then	be	released	and	the	cover	can	
be	opened	by	hand.	
When	a	cover	is	closed	it	should	be	locked	by	a	
shrouding	bolt	without	fail.	Tighten	the	shrouding	
bolt	to	a	torque	of	0.7	N·m.
Shrouding Bolt
Shrouding Bolt
F0501.ai
Figure 5.1
Shrouding Bolt
• Plug and seal an unused conduit connection.
5.2 Connections of External
Wiring to Terminal Box
5.2.1 Power Supply Wiring Connection
Connect	the	power	supply	wiring	to	the	SUPPLY	+	and	
–	terminals.
Power supply
–
+
Transmitter terminal box
F0502.ai
SUPPL
Y
PULSE
CHECK
ALARM
Figure 5.2
Power Supply Wiring Connection
5.2.2 Configuration Tool Connection
Connect	the	configuration	tool	to	the	SUPPLY	+	and	
–	terminals.	(Use	hooks.)
SUPPL
Y
PULSE
CHECK
ALARM
Transmitter terminal box
F0503.ai
Power supply
–
+
Ignore the polarity since
the configuration tool is
AC-coupled to the terminal
box.
USB
FieldMate Modem
PC/FieldMate
Figure 5.3
Configuration Tool Connection
5.2.3 Status Output Connection
When	option	code	/AL	is	specified,	connect	the	external	
wiring	as	shown	in	Figure	5.4.
To	configure	and	activate	the	process	alarm	function	and	
status	output,	it	is	necessary	to	set	some	parameters.	
Refer	to	each	communication	manual	for	procedures.
SUPPL
Y
PULSE
CHECK
ALARM
Transmitter
terminal box
Magnetic
valve
AC power supply
External power
supply 30V DC,
120mA max
+
–
250Ω
24V DC
Use two-wire separately shielded cables.
Distributor
Shielded cable
F0504.ai
Figure 5.4
Status Output Connection