<7. Errors and Countermeasures>

39

IM 01C25A01-01E

Integral

indicator

Cause

4-20mA Output

operation during error

Countermeasure

AL. 79

OV. DISP

Displayed value exceeds limit.

Continues to operate and output.

Check settings and change them as

needed.

AL.87

FLG. HI

Flange temperature exceeds a preset

upper limit.

It depends on the Diag Out Option

setting.

Off: Continue to operate and output.

Burnout:Outputs AO upper limit or AO

lower limit.

Fall back:Outputs Diag Out Fixed Val.

Check the heater failure.

Check the capsule temp. and

Amplifier temp.

Adjust Flg Temp Coef.

AL.87

FLG. LO

Flange temperature is below a preset

lower limit.

AL.88

INVR.DP

Differential pressure/pressure

fluctuation does not reach the reference

level required to blockage detection so

that no blockage detection is carried

out.

Continue to operate and output.

Check process condition.

AL.88

INVR.SL

Low-pressure-side fluctuation does not

reach the reference fluctuation level

required to blockage detection.

AL.88

INVR.SH

High-pressure-side fluctuation does not

reach the reference fluctuation level

required to blockage detection.

AL.88

INVR.F

BlkF can not be used for blockage

detection for some reasons.

AL.89

ILBD.OV

Appointed the diagnosis range outside.

AL.89

B BLK

B Blocking (both-side blockage) is

detected.

It depends on the Diag Out Option

setting.

Off: Continue to operate and output.

Burnout: Outputs AO upper limit or AO

lower limit.

Fall back: Outputs Diag Out Fixed Val.

Check process condition.

AL.89

H BLK

High-pressure-side blockage is

detected.

AL.89

L BLK

Low-pressure-side blockage is

detected.

AL.89

H LRG

Pressure fluctuation amplitude of high-

pressure side is large.

AL.89

L LRG

Pressure fluctuation amplitude of low-

pressure side is large.

AL.89

A BLK

A Blocking (single-side blockage) is

detected.

AL. 90 SIM

Under Simulation Mode for flow.

Simulate input output.

Check Simulation Mode.

AL. 91 F. SIM Under Simulation Mode for device

variables.

Output the setting value of Simulate-

Value

Check Simulation Mode

AL. 91 P. SIM
AL.91 SP. SIM
AL. 91

ET. SIM
AL. 91

TF. SIM
AL. 91

PCT. SIM
AL. 91

AO. SIM

Er

ro

rs

an

d C

ou

nte

rm

ea

su

re

s

7