2 routing the impulse piping – Yokogawa EJX115A User Manual
Page 26
 
<4. Installing Impulse Piping>
24
IM 01C25A01-01E
1) Screw nipples into the connection ports on the
transmitter side of the 3-valve manifold, and into
the impulse piping connecting ports on the process
connectors. (To maintain proper sealing, wind sealing
tape around the nipple threads.)
2) Mount the 3-valve manifold on the 50 mm (2-inch)
pipe by fastening a U-bolt to its mounting bracket.
Tighten the U-bolt nuts only lightly at this time.
3) Install the pipe assemblies between the 3-valve
manifold and the process connectors and lightly
tighten the ball head lock nuts. (The ball-shaped ends
of the pipes must be handled carefully, since they will
not seal properly if the ball surface is scratched or
otherwise damaged.)
4) Now tighten the nuts and bolts securely in the
following sequence:
Process connector bolts → transmitter-end ball head
lock nuts → 3-valve manifold ball head lock nuts →
3-valve manifold mounting bracket U-bolt nuts
Direct-Mounting Type 3-Valve Manifold
1) Mount the 3-valve manifold on the transmitter. (When
mounting, use the two gaskets and the four bolts
provided with the 3-valve manifold. Tighten the bolts
evenly.)
2) Mount the process connectors and gaskets on the top
of the 3-valve manifold (the side on which the impulse
piping will be connected.)
Bolts
Process
connector
Gasket
Gasket
Process
connector
Bolts
Stop valve
Stop valve
3-valve
manifold
3-valve
manifold
Equalizing valve
Equalizing
valve
Stop valve
Impulse
piping
Impulse
piping
Stop valve
F0404.ai
Figure 4.4 3-Valve Manifold (Direct-Mounting Type)
NOTE
After	completing	the	connection	of	the	transmitter	and	
3-valve	manifold,	be	sure	to	CLOSE	the	low	pressure	
and	high	pressure	stop	valves,	OPEN	the	equalizing	
valve,	and	leave	the	manifold	with	the	equalizing	valve	
OPEN.
You	must	do	this	in	order	to	avoid	overloading	the	
transmitter	from	either	the	high	or	the	low	pressure	
side	when	beginning	operation.
4.1.2 Routing the Impulse Piping
(1) Process Pressure Tap Angles
If condensate, gas, sediment or other extraneous
material in the process piping gets into the impulse
piping, pressure measurement errors may result. To
prevent such problems, the process pressure taps must
be angled as shown in Figure 4.5 according to the kind of
fluid being measured.
NOTE
• If the process fluid is a gas, the taps must be
vertical or within 45° either side of vertical.
• If the process fluid is a liquid, the taps must be
horizontal	or	below	horizontal,	but	not	more	than	
45°	below	horizontal.
• If the process fluid is steam or other condensing
vapor,	the	taps	must	be	horizontal	or	above	
horizontal,	but	not	more	than	45°	above	horizontal.
[Gas]
Pressure
taps
Process
piping
[Steam]
[Liquid]
45°
45°
45°
45°
45°
45°
F0405.ai
Figure 4.5
Process Pressure Tap Angle
(For Horizontal Piping)
(2) Position of Process Pressure Taps and
Transmitter
If	condensate	(or	gas)	accumulates	in	the	impulse	piping,	
it	should	be	removed	periodically	by	opening	the	drain	
(or	vent)	plugs.	However,	this	will	generate	a	transient	
disturbance	in	the	pressure	measurement,	and	therefore	
it	is	necessary	to	position	the	taps	and	route	the	impulse	
piping	so	that	any	extraneous	liquid	or	gas	generated	in	
the	leadlines	returns	naturally	to	the	process	piping.
• If the process fluid is a gas, then as a rule the
transmitter	must	be	located	higher	than	the	process	
pressure	taps.
• If the process fluid is a liquid or steam, then as a
rule	the	transmitter	must	be	located	lower	than	the	
process	pressure	taps.
(3) Impulse Piping Slope
The	impulse	piping	must	be	routed	with	only	an	upward	or	
downward	slope.	Even	for	horizontal	routing,	the	impulse	
piping	should	have	a	slope	of	at	least	1/10	to	prevent	
condensate	(or	gases)	from	accumulating	in	the	pipes.