2 routing the impulse piping – Yokogawa EJX115A User Manual

Page 26

Advertising
background image

<4. Installing Impulse Piping>

24

IM 01C25A01-01E

1) Screw nipples into the connection ports on the

transmitter side of the 3-valve manifold, and into

the impulse piping connecting ports on the process

connectors. (To maintain proper sealing, wind sealing

tape around the nipple threads.)

2) Mount the 3-valve manifold on the 50 mm (2-inch)

pipe by fastening a U-bolt to its mounting bracket.

Tighten the U-bolt nuts only lightly at this time.

3) Install the pipe assemblies between the 3-valve

manifold and the process connectors and lightly

tighten the ball head lock nuts. (The ball-shaped ends

of the pipes must be handled carefully, since they will

not seal properly if the ball surface is scratched or

otherwise damaged.)

4) Now tighten the nuts and bolts securely in the

following sequence:

Process connector bolts → transmitter-end ball head

lock nuts → 3-valve manifold ball head lock nuts →

3-valve manifold mounting bracket U-bolt nuts

Direct-Mounting Type 3-Valve Manifold

1) Mount the 3-valve manifold on the transmitter. (When

mounting, use the two gaskets and the four bolts

provided with the 3-valve manifold. Tighten the bolts

evenly.)

2) Mount the process connectors and gaskets on the top

of the 3-valve manifold (the side on which the impulse

piping will be connected.)

Bolts

Process

connector

Gasket

Gasket

Process

connector

Bolts

Stop valve

Stop valve

3-valve

manifold

3-valve

manifold

Equalizing valve

Equalizing

valve

Stop valve

Impulse

piping

Impulse

piping

Stop valve

F0404.ai

Figure 4.4 3-Valve Manifold (Direct-Mounting Type)

NOTE

After completing the connection of the transmitter and
3-valve manifold, be sure to CLOSE the low pressure
and high pressure stop valves, OPEN the equalizing
valve, and leave the manifold with the equalizing valve
OPEN.
You must do this in order to avoid overloading the
transmitter from either the high or the low pressure
side when beginning operation.

4.1.2 Routing the Impulse Piping

(1) Process Pressure Tap Angles

If condensate, gas, sediment or other extraneous

material in the process piping gets into the impulse

piping, pressure measurement errors may result. To

prevent such problems, the process pressure taps must

be angled as shown in Figure 4.5 according to the kind of

fluid being measured.

NOTE

• If the process fluid is a gas, the taps must be

vertical or within 45° either side of vertical.

• If the process fluid is a liquid, the taps must be

horizontal or below horizontal, but not more than
45° below horizontal.

• If the process fluid is steam or other condensing

vapor, the taps must be horizontal or above
horizontal, but not more than 45° above horizontal.

[Gas]

Pressure

taps

Process

piping

[Steam]

[Liquid]

45°

45°

45°

45°

45°

45°

F0405.ai

Figure 4.5

Process Pressure Tap Angle

(For Horizontal Piping)

(2) Position of Process Pressure Taps and

Transmitter

If condensate (or gas) accumulates in the impulse piping,
it should be removed periodically by opening the drain
(or vent) plugs. However, this will generate a transient
disturbance in the pressure measurement, and therefore
it is necessary to position the taps and route the impulse
piping so that any extraneous liquid or gas generated in
the leadlines returns naturally to the process piping.

• If the process fluid is a gas, then as a rule the

transmitter must be located higher than the process
pressure taps.

• If the process fluid is a liquid or steam, then as a

rule the transmitter must be located lower than the
process pressure taps.

(3) Impulse Piping Slope

The impulse piping must be routed with only an upward or
downward slope. Even for horizontal routing, the impulse
piping should have a slope of at least 1/10 to prevent
condensate (or gases) from accumulating in the pipes.

Advertising