5 emc conformity standards, Emc conformity standards, Caution – Yokogawa EJX115A User Manual

Page 17

Advertising
background image

<2. Handling Cautions>

15

IM 01C25A01-01E

• Ex ia IIC T4, Ex nL IIC T4

• Ambient Temperature: –50 to 60°C

• Max. Process Temp.: 120°C

• Enclosure: IP66/IP67

Note 2. Entity Parameters

• Intrinsically safe ratings are as follows:

Maximum Input Voltage (Vmax/Ui) = 30 V

Maximum Input Current (Imax/Ii) = 200 mA

Maximum Input Power (Pmax/Pi) = 0.9 W

Maximum Internal Capacitance (Ci) = 10 nF

Maximum Internal Inductance (Li) = 0 µH

• Type "n" ratings are as follows:

Maximum Input Voltage (Vmax/Ui) = 30 V

Maximum Internal Capacitance (Ci) = 10 nF

Maximum Internal Inductance (Li) = 0 µH

• Installation Requirements

Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,

Co ≥ Ci + Ccable, Lo ≥ Li + Lcable

Voc ≤ Vmax, Isc ≤ Imax,

Ca ≥ Ci + Ccable, La ≥ Li + Lcable

Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are

parameters of barrier.

Note 3. Installation

• In any safety barrier used output current must be

limited by a resistor 'R' such that Io=Uo/R.

• The safety barrier must be IECEx certified.

• Input voltage of the safety barrier must be less

than 250 Vrms/Vdc.

• The instrument modification or parts replacement

by other than authorized representative of

Yokogawa Electric Corporation and will void IECEx

Intrinsically safe and type n certification.

F0216.ai

EJX Series Pressure

Transmitters

IECEx certified

Safety Barrier

Supply

Hazardous Location

Nonhazardous Location

General

Purpose

Equipment

+

+

+

+

[Intrinsically Safe]

Group IIC, Zone 0

F0217.ai

EJX Series Pressure

Transmitters

Supply

Hazardous Location

Nonhazardous Location

+

+

Not Use

Safety Barrier

[type n]

IECEx Certified

Equipment [nL]

EJX Series Pressure

Transmitters

Group IIC, Zone 2

b. IECEx Flameproof Type

Caution for IECEx flameproof type.

Note 1. Model EJX/EJA-E Series pressure transmitters

with optional code /SF2 or /SU2 are applicable
for use in hazardous locations:

• No. IECEx CSA 07.0008
• Applicable Standard: IEC60079-0:2004,

IEC60079-1:2003

• Flameproof for Zone 1, Ex d IIC T6...T4
• Enclosure: IP66/IP67
• Maximum Process Temperature: 120°C (T4),

100°C (T5), 85°C (T6)

• Ambient Temperature: –50 to 75°C (T4),

–50 to 80°C (T5), –50 to 75°C (T6)

• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA dc

Note 2. Wiring

• In hazardous locations, the cable entry devices

shall be of a certified flameproof type, suitable for
the conditions of use and correctly installed.

• Unused apertures shall be closed with suitable

flameproof certified blanking elements.

Note 3. Operation

• WARNING:

AFTER DE-ENERGIZING, DELAY 5 MINUTES
BEFORE OPENING.

• WARNING:
WHEN AMBIENT TEMPERATURE ≥ 65°C, USE

THE HEAT-RESISTING CABLES ≥ 90°C.

• Take care not to generate mechanical sparking

when accessing to the instrument and peripheral
devices in a hazardous location.

Note 4. Maintenance and Repair

• The instrument modification or parts replacement

by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void IECEx Certification.

2.5 EMC Conformity Standards

EN61326-1 Class A, Table 2 (for use in industrial
locations)
EN61326-2-3

CAUTION

To meet EMC regulations, Yokogawa recommends
that customers run signal wiring through metal
conduits or use shielded twisted-pair cabling when
installing EJX/EJA-E Series transmitters in a plant.

H

an

dlin

g C

au

tio

ns

2

Advertising