Installation, 1 mounting, 2 mounting the diaphragm seals – Yokogawa EJX115A User Manual

Page 20: Mounting, Mounting the diaphragm seals, Important, 2 mounting the diaphragm seals important

Advertising
background image

<3. Installation>

18

IM 01C25A01-01E

3. Installation

IMPORTANT

• When welding piping during construction, take

care not to allow welding currents to flow through
the transmitter.

• Do not step on this instrument after installation.
• For EJ430, EJ440 and EJ438,

the atmospheric opening is located on the low
pressure side cover flange. For EJ530 and
EJX630A whose capsule code is A, B, or C, the
pipe of the atmospheric opening is located on the
pressure detecting section. These openings must
not face upward.

F00301.ai

Capsule code

Zero-adjustment screw

Pipe

(backside of the instrument)

6

Figure 3.1

EJ530 and EJX630A Horizontal

Mounting Position

3.1 Mounting

■ The transmitter can be mounted on a nominal

50 mm (2-inch) pipe using the mounting bracket
supplied, as shown in Figure 3.2 and 3.3. Tighten the
(four) bolts that hold the transmitter with a torque of
approximately 39 N·m {4 kgf·m}.

Transmitter

mounting bolt

U-bolt nut

Mounting bracket

50 mm(2-inch) pipe

U-bolt

F0302.ai

Figure 3.2

Transmitter Mounting

(Horizontal Impulse Piping Type)

Vertical pipe mounting

(Process connector upside)

Transmitter

mounting bolt

Mounting

bracket

U-bolt nut

U-bolt

50 mm

(2-inch) pipe

Vertical pipe mounting

(Process connector downside)

F0303.ai

Figure 3.3

Transmitter Mounting

(Vertical Impulse Piping Type)

Vertical pipe mounting

50 mm

(2-inch) pipe

U-bolt (L)

U-bolt (S)

Mounting

bracket

U-bolt

nut (S)

U-bolt nut (L)

Horizontal pipe mounting

F0304.ai

Figure 3.4

EJ510 and EJ530 Mounting

3.2 Mounting the Diaphragm Seals

IMPORTANT

• Please use a gasket with an inside diameter (ød)

that is greater than the diameter of the diaphragm
seal. If a gasket with a smaller inside diameter is
used, the diaphragm may not function correctly.

• During the diaphragm seal installation, ensure as

far as possible that no seal liquid head pressure is
applied to the diaphragm seals.

• Exercise care so as not to damage diaphragm

surfaces. Since the diaphragm protrudes approx.
1 mm from the flange surface, do not place the
pressure detector section face down on a surface
as this can damage the diaphragm.

• Do not sharply bend or twist capillary tube or apply

excessive stress to them.

• Never loosen the four bolts securing the cover

flange or the screws at the joints between the
capillary tube and cover flanges. If the seal liquid
leaks, the transmitter cannot be used.