Wiring, 1 wiring precautions, 2 connections of external wiring to terminal box – Yokogawa EJX115A User Manual

Page 30: Wiring precautions, Connections of external wiring to terminal box, 1 wiring precautions important, 1 power supply wiring connection, 2 configuration tool connection, 3 status output connection

Advertising
background image

<5. Wiring>

28

IM 01C25A01-01E

5. Wiring

NOTE

For F

OUNDATION

Fieldbus and PROFIBUS PA

communication types, please refer to manuals in the
attached CD-ROM.

5.1 Wiring Precautions

IMPORTANT

• Lay wiring as far as possible from electrical noise

sources such as large capacity transformers,
motors, and power supplies.

• Remove electrical connection dust cap before

wiring.

• All threaded parts must be treated with

waterproofing sealant. (A non-hardening silicone
group sealant is recommended.)

• To prevent noise pickup, do not pass signal and

power cables through the same ducts.

• Explosion-protected instruments must be wired

in accordance with specific requirements (and,
in certain countries, legal regulations) in order
to preserve the effectiveness of their explosion-
protected features.

• The terminal box cover is locked by an Allen head

bolt (a shrouding bolt) on ATEX flameproof type
transmitters. When the shrouding bolt is driven
clockwise using an Allen wrench, it gose in. The
cover lock can then be released and the cover can
be opened by hand.
When a cover is closed it should be locked by a
shrouding bolt without fail. Tighten the shrouding
bolt to a torque of 0.7 N·m.

Shrouding Bolt

Shrouding Bolt

F0501.ai

Figure 5.1

Shrouding Bolt

• Plug and seal an unused conduit connection.

5.2 Connections of External

Wiring to Terminal Box

5.2.1 Power Supply Wiring Connection

Connect the power supply wiring to the SUPPLY + and
– terminals.

Power supply

+

Transmitter terminal box

F0502.ai

SUPPL

Y

PULSE

CHECK

ALARM

Figure 5.2

Power Supply Wiring Connection

5.2.2 Configuration Tool Connection

Connect the configuration tool to the SUPPLY + and
– terminals. (Use hooks.)

SUPPL

Y

PULSE

CHECK

ALARM

Transmitter terminal box

F0503.ai

Power supply

+

Ignore the polarity since

the configuration tool is

AC-coupled to the terminal

box.

USB

FieldMate Modem

PC/FieldMate

Figure 5.3

Configuration Tool Connection

5.2.3 Status Output Connection

When option code /AL is specified, connect the external
wiring as shown in Figure 5.4.
To configure and activate the process alarm function and
status output, it is necessary to set some parameters.
Refer to each communication manual for procedures.

SUPPL

Y

PULSE

CHECK

ALARM

Transmitter

terminal box

Magnetic

valve

AC power supply

External power

supply 30V DC,

120mA max

+

250Ω

24V DC

Use two-wire separately shielded cables.

Distributor

Shielded cable

F0504.ai

Figure 5.4

Status Output Connection

Advertising