<5. Wiring>

31

IM 01C25A01-01E

5.3.2 Wiring Installation

(1) General-use Type and Intrinsically Safe

Type

With the cable wiring, use a metallic conduit or waterproof
glands.

• Apply a non-hardening sealant to the terminal box

connection port and to the threads on the flexible
metal conduit for waterproofing.

F0511.ai

Flexible metal conduit

Wiring metal

conduit

Tee

Drain plug

Apply a non-hardening

sealant to the threads for

waterproofing.

Figure 5.10 Typical Wiring Using Flexible Metal

Conduit

(2) Flameproof Type

Wire cables through a flameproof packing adapter, or use
a flameproof metal conduit.

Wiring cable through flameproof packing adapter.

• Apply a non-hardening sealant to the terminal box

connection port and to the threads on the flameproof
packing adapter for waterproofing.

Flameproof packing

adapter

Flexible metal conduit

Wiring metal

conduit

Tee

Drain plug

Apply a non-hardening

sealant to the threads for

waterproofing.

F0512.ai

Figure 5.11 Typical Cable Wiring Using Flameproof

Packing Adapter

Flameproof metal conduit wiring

• A seal fitting must be installed near the terminal box

connection port for a sealed construction.

• Apply a non-hardening sealant to the threads of the

terminal box connection port, flexible metal conduit
and seal fitting for waterproofing.

F0513.ai

Non-hazardous area

Hazardous area
Flameproof

heavy-gauge

steel conduit

Tee

Drain plug

Seal fitting

Gas sealing device

Flameproof flexible

metal conduit

Apply a non-hardening

sealant to the threads of

these fittings for

waterproofing

After wiring, impregnate the fitting

with a compound to seal tubing.

Figure 5.12 Typical Wiring Using Flameproof Metal

Conduit

5.4 RTD Cable Connection

(EJX910A/EJX930A)

Connection of the RTD cable is always required to
measure external temperature. Follow the procedures
below to connect a cable when a cable gland or a conduit
is used.

5.4.1 Connecting Shielded Cable with

Cable Gland (External temperature

input code: -1, -2, -3, and -4)

• RTD connection components: EJX multivariable

transmitter, two cable glands, and RTD cable.
Two cable glands are attached.

Transmitter

Cable gland

Electrical connection

RTD cable

with connector

Detail of connector

F0514.ai

Y

L

P

P

U

S

ESL

UP

K

C

E

H

C

M

R

A

L

A

• Magnified view of the RTD connector in the

transmitter's terminal box.

SUPPL

Y

PULSE

CHECK

ALARM

SUPPL

Y

PULSE

CHECK

ALARM

Protection Cap

Connecting Port

F0515.ai

The RTD cable connecting port is covered with a cap to
keep out dust. The cap should not be removed until you
are ready to install the cable.

W

irin

g

5