<5. Wiring>

34

IM 01C25A01-01E

5.5 Grounding

Grounding is always required for the proper operation of
transmitters. Follow the domestic electrical requirements
as regulated in each country. For a transmitter with a
built-in lightning protector, grounding should satisfy
ground resistance of 10Ω or less.
Ground terminals are located on the inside and outside of
the terminal box. Either of these terminals may be used.

Ground terminal

(inside)

Ground terminal

(outside)

F0525.ai

SUPPL

Y

PULSE

CHECK

ALARM

Figure 5.14 Ground Terminals

5.6 Power Supply Voltage and

Load Resistance

When configuring the loop, make sure that the external
load resistance is within the range in the figure below.

(Note) In case of an intrinsically safe transmitter, external load

resistance includes safety barrier resistance.

600

250

0

10.5 16.6

25.2

42

External

load

resistance

R (Ω)

Power supply voltage E (V DC)

F0526.ai

Communication

applicable range

BRAIN and HART

R= E–10.5

0.0244

Figure 5.15 Relationship between Power Supply

Voltage and External Load Resistance