Errors and countermeasures – Yokogawa EJX115A User Manual

Page 39

Advertising
background image

<7. Errors and Countermeasures>

37

IM 01C25A01-01E

7. Errors and Countermeasures

NOTE

For HART protocol revision 7, F

OUNDATION

Fieldbus, and PROFIBUS PA communication types, please refer to manuals

in the attached CD-ROM.

The table below shows a summary of error messages for BRAIN and HART (protocol revision 5) protocols.

Table 7.1

Alarm Message Summary (Except EJX910A and EJX930A)

Indicator

Cause

Output Operation

during Error

Countermeasure

None
AL. 01

CAP. ERR

Sensor problem.

Outputs the signal (Hold, High, or

Low) set with parameter.

Replace capsule when error keeps

appearing even after restart.

Capsule temperature sensor problem.
Capsule EEPROM problem.

AL. 02

AMP. ERR

Amplifier temperature sensor problem. Outputs the signal (Hold, High, or

Low) set with parameter.

Replace amplifier.

Amplifier EEPROM problem.
Amplifier problem.

AL. 10

PRESS

Input is outside measurement range

limit of capsule.

Outputs high range limit value or low

range limit value.

Check input or replace capsule when

necessary.

AL. 11

ST. PRSS

Static pressure exceeds limit.

Continues to operate and output.

AL. 12

CAP. TMP

Capsule temperature is outside range

(–50 to 130°C).

Use heat insulation or make lagging

to keep temperature within range.

AL. 13

AMP. TMP

Amplifier temperature is outside range

(–50 to 95°C).

AL. 30

RANGE

Output is outside upper or lower range

limit value.

Outputs high range limit value or low

range limit value.

Check input and range setting, and

change them as needed.

AL. 31

SP. RNG

Static pressure exceeds specified

range.

Holds output immediately before error

occurred.

AL. 35 *

1

P. HI

Input pressure exceeds specified

threshold.

Continues to operate and

output.

Check input.

AL. 36 *

1

P. LO
AL. 37 *

1

SP. HI

Input static pressure exceeds specified

threshold.

AL. 38 *

1

SP. LO
AL. 39 *

1

TMP. HI

Detected temperature exceeds

specified threshold.

AL. 40 *

1

TMP. LO
AL. 50

P. LRV

Specified value is outside of setting

range.

Holds output immediately before error

occurred.

Check setting and change them as

needed.

AL. 51

P. URV
AL. 52

P. SPN
AL. 53

P. ADJ

Continues to operate and output.

Check input.

AL. 54

SP. RNG

Continues to operate and output

holding static pressure in %.

Check setting and change them as

needed.

AL. 55

SP. ADJ

Continues to operate and output.

Check input.

AL. 60

SC. CFG

Specified values or settings to define

signal characterizer function do not

satisfy the condition.

Check setting and change

them as needed.

AL. 79

OV. DISP

Displayed value exceeds limit.

*1: These alarms may appear only when process alarm function is activated.