<2. Handling Cautions>

6

IM 01C25A01-01E

2.1 Model and Specifications

Check

The model name and specifications are indicated on the
name plate attached to the case.

F0203.ai

Figure 2.2 Name Plate

2.2 Selecting the Installation

Location

The transmitter is designed to withstand severe
environmental conditions. However, to ensure that it will
provide years of stable and accurate performance, take
the following precautions when selecting the installation
location.
(a) Ambient Temperature

Avoid locations subject to wide temperature variations
or a significant temperature gradient. If the location is
exposed to radiant heat from plant equipment, provide
adequate thermal insulation and/or ventilation.

(b) Ambient Atmosphere
Do not install the transmitter in a corrosive

atmosphere. If this cannot be avoided, there must be
adequate ventilation as well as measures to prevent
the leaking of rain water and the presence of standing
water in the conduits.

(c) Shock and Vibration
Although the transmitter is designed to be relatively

resistant to shock and vibration, an installation site
should be selected where this is kept to a minimum.

(d) Installation of Explosion-protected Transmitters
An explosion-protected transmitters is certified for

installation in a hazardous area containing specific
gas types. See subsection 2.4 “Installation of an
Explosion-Protected Instrument.”

2.3 Pressure Connection

WARNING

• Never loosen the process connector bolts when an

instrument is installed in a process. The device is
under pressure, and a loss of seal can result in a
sudden and uncontrolled release of process fluid.

• When draining toxic process fluids that have

condensed inside the pressure detector, take
appropriate steps to prevent the contact of such
fluids with the skin or eyes and the inhalation of
vapors from these fluids.

The following precautions must be observed in order to
safely operate the transmitter under pressure.

(a) Make sure that the process connector bolts are

tightened firmly.

(b) Make sure that there are no leaks in the impulse

piping.

(c) Never apply a pressure higher than the specified

maximum working pressure.

2.4 Installation of an Explosion-

Protected Instrument

NOTE

For F

oundation

Fieldbus and PROFIBUS PA explosion

protected type, please refer to manual in the attached
CD-ROM.

If a customer makes a repair or modification to an
intrinsically safe or explosionproof instrument and the
instrument is not restored to its original condition, its
intrinsically safe or explosionproof construction may be
compromised and the instrument may be hazardous to
operate. Please contact Yokogawa before making any
repair or modification to an instrument.

CAUTION

This instrument has been tested and certified as
being intrinsically safe or explosionproof. Please
note that severe restrictions apply to this instrument’s
construction, installation, external wiring, maintenance
and repair. A failure to abide by these restrictions could
make the instrument a hazard to operate.

WARNING

Maintaining the safety of explosionproof equipment
requires great care during mounting, wiring, and
piping. Safety requirements also place restrictions on
maintenance and repair. Please read the following
sections very carefully.

WARNING

The range setting switch must not be used in a
hazardous area.