Yokogawa Removable Chassis DX1000N User Manual

Page 324

Advertising
background image

App-6

IM 04L41B01-01E

File Output Example

Below is a manual sample data example of channels 1, 2, 3, and 4.

YREC
Manual Sample Data Version 1.02.00
Model

DX1000

Language Code

shift-JIS

File Status

Progress

Serial No.

S5E701600

File Header
Ch

CH001

CH002

CH003

CH004

Ch Id

TI-101

OUT-102

FI-103

VA-204

Tag

abc

def

hij

klmn

Unit

°C

V

m3/h

%

2005/10/01 08:57:22 213.8

0.517

368.4

68.9

2005/10/01 08:57:28 208.6

0.494

363.0

68.1

Note

• Output when error data, overrange data, or computation overflow data is detected

Channel

Data

Output

Measurement channels

Error

(Space)

+over range (includes burnout detection)

99999

–over range (includes burnout detection)

–99999

Computation channel

Error

999999999

Positive computation overflow

999999999

(when the value exceeds 99999999)
Negative computation overflow

–999999999

(when the value falls below –9999999)
The decimal place that was specified when the span for

the channel was specified applies to the output values. For

example, if the span setting of the channel is “200.0,” then

“999999999” is output when the value exceeds “9999999.9”

and “–999999999” is output when the value is below “–

999999.9.”

• A new manual sampled data file is created in the following cases.

• A measurement channel is changed to

Skip from a range other than Skip.

• A measurement channel is changed from

Skip to a range other than Skip.

• A computation channel is changed from

On to Off or Off to On.

• The unit is changed.

Appendix 3 Text File Data Format

Advertising
This manual is related to the following products: