4 data storage function, 4 data storage function -26, Data types – Yokogawa Removable Chassis DX1000N User Manual

Page 37

Advertising
background image

1-26

IM 04L41B01-01E

1.4 Data Storage Function

This section explains the types of data that the DX can record and how to store them.
For information about the data storage function on DXs with the /AS1 advanced
security option, see the Advanced Security Function (/AS1) User’s Manual,
IM04L41B01-05EN
.

Data Types

The types of data that the DX can record are as follows:

Data Type

Description

Display data

• Waveform data displayed on the trend display. The measured data is recorded

as a specified sampling interval. The sampling interval is specified using the

trend interval.

• The minimum and maximum values among the measured data within the

sampling interval are saved.

• A header string (common to other files) can be written in the file.
• The display data contains alarm and message information.
• Data format: Binary (Undisclosed)

Event data

• Measured data that is recorded at a specified sampling interval. There are two

modes. One mode starts recording when a trigger event occurs. The other

mode records at all times.

• A header string (common to other files) can be written in the file.
• The event data contains alarm and message information.
• Data format: Binary (Undisclosed)

Manual sampled

data

• Instantaneous value of the measured data when a manual sample operation is

executed.

• A header string (common to other files) can be written in the file.
• Data format: Text

Report data

(/M1 and /PM1

options)

• Hourly, daily, weekly, and monthly report data. Report data is created at an

interval that is determined by the report type (one hour for hourly reports, one

day for daily reports, and so on).

• A header string (common to other files) can be written in the file.
• Data format: Text
• The data can be converted to XML spreadsheet data (release numbers 4 and

later).

Snapshot data

(screen image

data)

• The image data of the DX screen when the snapshot operation is executed.
• The data can be saved to a CF card.
• Data format: PNG

Setup data

• The setup data of the DX.
• Data format: Binary (Undisclosed)

Custom Display

Setup Data

• The custom display setup data of the DX.
• Data format: text

• Display data and event data

Display data can be likened to the conventional recording on the chart sheet and

are useful for long-term recording. Event data is useful when you wish to record the
measured data in detail.

Measured data per

scan interval

Display data

Event data

Sampling interval of display data

Scan interval

Time

Sampling interval of event data

Maximum value per sampling interval

Minimum value per sampling interval

Instantaneous value during sampling

Advertising
This manual is related to the following products: