Chapter 3 measurement channels and alarms – Yokogawa Removable Chassis DX1000N User Manual

Page 95

Advertising
background image

Measurement Channels and

Alarms

IM 04L41B01-01E

3-1

1

2

3

4

5

6

7

8

9

10

11

12

App

Index

3.1 Setting the Scan Interval and the Integration

Time of the A/D Converter

Select the scan interval and the integration time of the A/D converter.
For a description of the scan interval and the integration time of the A/D converter, see
section 1.1.

Setup Screen

Press

MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic

setting mode), and select the

Menu tab > A/D, Memory.

Setup Items

• Scan interval > Scan mode

Normal: Measures at the normal mode scan interval.

* The scan mode is fixed at Normal when the multi batch function (/BT2 option; release

numbers 3 and later) is being used.

FAST: Measures at a scan interval of 25 ms (DX1002, DX1004, DX1002N, and

DX1004N) or 125 ms (DX1006, DX1012, DX1006N, and DX1012N).

• Scan interval > Scan interval

The selectable settings appear.

• Scan interval > A/D integrate

When the scan mode is set to

Normal, select the A/D integration time as necessary.

Only the selectable settings are displayed.

Settings Description
Auto

The DX automatically detects the power supply frequency and sets the integration

time to 16.7 ms and 20 ms for 60 Hz and 50 Hz, respectively. Fixed to 20 ms on

/P1 models that use the 24 VDC power supply.

50Hz

Sets the integration time to 20 ms.

60Hz

Sets the integration time to 16.7 ms.

100ms

Sets the integration time to 100 ms (when the scan interval is 2 s or 5 s).

600Hz

The A/D integration time for fast sampling mode. You cannot change this value.

Chapter 3

Measurement Channels and Alarms

Advertising
This manual is related to the following products: