Setup items – Yokogawa Removable Chassis DX1000N User Manual

Page 79

Advertising
background image

2-12

IM 04L41B01-01E

• Status Relay Details

Press

MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic

setting mode), and select the

Menu tab > Status Relay > Status Relay Details.

Setup Items

• Relay Action > Fail Relay, Status Relay (Release numbers 4 and later)

On DXs without the /AS1 advanced security option

Setting

Description

Fail

Outputs a fail relay.

Status relay

Outputs a status relay. Even if you set both relays to “Status relay,” you

cannot make them output different statuses.

On DXs with the /AS1 advanced security option

Setting

Description

Fail

Outputs a fail relay.

Status relay

Outputs a status relay. Even if you set both relays to “Status relay,” you

cannot make them output different statuses.

Mem. sample*

Relay output continues from memory start until memory stop.

Invalid user

Relay output continues from when a user is determined to be invalid until a

Locked ACK command is executed.

Login

Relay output occurs whenever a user is logged in.

* When the multi batch function (/BT2 option) is being used, relay output starts when memory

start occurs for any of the batches, and relay output stops when memory stop occurs for all
the batches.

• Status Relay Details > Memory/Media status

On: The status of the internal memory and the CF card is relayed.

• Status Relay Details > Measurement error

On: A relay signal is output when a measurement error occurs.

• Status Relay Details > Communication error

On: A relay signal is output when a communication error occurs.

• Status Relay Details > Memory stop

On: A relay signal is output when memory sampling stops.

* When the multi batch function (/BT2 option) is being used, relay output starts when

recording stops for all the batches.

• Status Relay Details > Alarm (Release numbers 3 and later)

On: Outputs a relay signal when one or more alarms occur. Alarms whose indications

are hidden (see section 3.6 for details) do not cause relay signal output. Relay output
ceases after all alarms are released (if no other relay output conditions are met).

2.9 Outputting the DX Status via the Relay Contact (/F1 and /F2 Options)