1.9 FAIL/Status Output Function (/F1 Option)

Output Relay Operation Assignment (Release numbers 4 and later)

For this function, there are relays labeled “FAIL” and “Status” on the rear panel.
You can assign the operations explained below to these two relays. On a relay that has
been set to “Status relay,” you must also set the DX status that will be relayed.

FAIL Output

When a failure occurs in the CPU of the DX, a relay contact signal (1 signal) is output.
The relay is energized when the CPU is normal and de-energizes when a CPU failure
occurs. Therefore, relay output is carried out also when the power is turned OFF (including
a power failure). You cannot change this behavior.

Relay Operation

NO

C

NC

During normal operation

NO

C

NC

When a failure occurs

NO

C

NC

When power is turned OFF

If a failure occurs, contact your nearest YOKOGAWA dealer for repairs.

Memory Sample Relay (Only on DXs with the /AS1 advanced security option)

The relay is energized at memory start and de-energized at memory stop. You cannot
change this behavior
When the multi batch function (/BT2 option) is being used, memory start is when memory
start occurs for any of the batches, and memory stop is when memory stop occurs for all
the batches.

Relay Operation

NO

C

NC

Memory sampling

NO

C

NC

Memory sampling stopped

NO

C

NC

When power is turned OFF

Invalid User Relay (Only on DXs with the /AS1 advanced security option)

The relay is energized when the user is invalid and de-energized when you execute the
Locked ACK command. You cannot change this behavior

Relay Operation

NO

C

NC

Normal

NO

C

NC

Invalid user

NO

C

NC

When power is turned OFF

User Login Status Relay (Only on DXs with the /AS1 advanced security option)

The relay is energized when a user is logged in (through key operations or through
communication commands) to the DX. You cannot change this behavior

Relay Operation

NO

C

NC

Not logged in

NO

C

NC

Logged in

NO

C

NC

When power is turned OFF