Setting the Match Time Timer

You can set the time match condition that is used for the event action function. These
timers are also used in TLOG computation.

For an explanation of the event action function, see section 7.1.

Display

Press MENU and then select Menu tab > Timer, Event action > MatchTimeTimer.

Settings

You cannot change these settings during memory sampling or computation.

• Timer number

You can set four match time conditions (1 to 4).

• Kind

Setting

Description

Day

Sets the time match condition for a day.

Week

Sets the time match condition for a week.

Month

Sets the time match condition for a month.

Year

Sets the time match condition for a year.

Set the items with check marks in the following table according to the Kind setting.

Settings

Kind

Day

Week

Month

Year

Month

Day

Day of the week

Hour:Minute

• Month

Set the month.

• Day

Set the day.

• Day of the week

Set the day of the week.

• Hour:Minute

Set the time in the range of 00:00 to 23:59.

• Timer action

Setting

Description

Single

Executes the action once when the condition is met.
You can reset a timer by pressing FUNC after the timer expires.

Repeat

Executes the action each time the condition is met.