Settings, Event data recording conditions, Disp data > trend/storage interval – Yokogawa Button Operated MV2000 User Manual

Page 96

Advertising
background image

4-2

M-4660

• Event Data Recording Conditions

Press MENU and then select > Menu tab > Data save > Event data.

Settings

• Memory > Data Kind

Setting

Description

Display

Records display data.

E+D

Records display data and event data. You cannot select this setting if the
trend update interval switching function (Trend rate switching) is set to on
On (see section 6.3 for details)

Event

Records event data.

• Memory sample > On/Off

Select On for the target channels.

• Disp data > Trend/Storage interval

Set the display trend/storage interval. For the trend/storage intervals that can only be

set on high-speed input models, 5 s/div and 10 s/div, 1 division (div) is equal to 40
dots.

You can only set trend/storage intervals that are longer than the scan interval you set

in Basic Setting Mode.

• Disp data > Save interval (when recording display data)

Set the size of recorded data files. Recorded data is divided into files of the size

specified here. The values that you can set here vary depending on the Trend/Storage
interval setting.

Trend/Storage
interval

1

5s

2

10s

2

15s

3

30s

1min

Sampling interval

125ms

250ms

500ms

1s

2s

Selectable Save
Interval Values

10 min to 12 h

10 min to 1
day

10 min to 3
days

10 min to 7
days

10 min to 14
days

Trend/Storage
interval

1

2min

5min

10min

15min

20min

Sampling interval

4s

10s

20s

30s

40s

Selectable Save
Interval Values

10 min to 14
days

10 min to 31
days

10 min to 31
days

10 min to 31
days

1 h to 31 days

Trend/Storage
interval

1

30min

1h

2h

4h

10h

Sampling interval

1h

2h

4h

8h

20h

Selectable Save
Interval Values

1 h to 31 days

1 h to 31 days

2 h to 31 days

4 h to 31 days

8 h to 31 days

1 You can only set a data interval that corresponds to a sampling interval that is slower than

the scan interval.

2 Only available on high-speed input models of the MV.
3 Selectable in fast sampling mode on medium-speed input models of the MV.

4.1 Setting the Recording Conditions of Measured Data