About TimerReset

If Event is set to Relay, Switch, MatchTimeTimer, or Alarm, TimerReset will not result

in a timeout (an action will not be executed even if the timer is used as an event).

If Event is set to Remote or UserKey, a timeout will occur (if the timer is used as an

event, an action will be executed).

About PanelLoad

PanelLoad can only be specified as an action when Event is set to Remote.
PanelLoad loads a setup data file, LOAD1.PDL, LOAD2.PDL, or LOAD3.PDL, in

the root directory of the CF card onto the MV, and uses it to configure the MV. Only
settings that pertain to Setting Mode are updated.

You must create a setup file and save it to the CF card in advance.

Event Trigger Operation

When Event is set to Relay, Switch, or Alarm:
The Trigger action will always occur when an output relay is activated, when an

internal switch is set to 1, or when an alarm occurs. However, the number of times the
trigger is activated depends on the event data mode (Single or Repeat).

About TimeAdjust

TimeAdjust can only be specified as an action when Event is set to Remote.

TimeAdjust sets the MV internal clock to the closest hour.

• Operation When the MV is Not Memory Sampling

Difference from the Nearest Hour Operation
0 s to 1 min 59 s

Truncates the minutes and seconds.
Example: 10 hours 01 min 50 s becomes 10 hours 00
min 00 s.

2 min to 57 min 59 s

The time is not changed.

58 min to 59 min 59 s

Rounds up the minutes and seconds.
Example: 10 hours 59 min 50 s becomes 11 hours 00
min 00 s.

• Operation When the MV is Memory Sampling (See section 1.11 for

details.)

If the time difference between the time when the remote control signal is applied

and the nearest hour is within the preset time, the time is gradually corrected.
Otherwise, the time is corrected immediately.

1.7 Event Action Function