Yokogawa Button Operated MV2000 User Manual

Page 51

Advertising
background image

1-44

M-4660

• Data That Can Be Used in Equations

The data listed below can be used in equations.

Data

Notation

Description

Measurement channel data

001, etc.

Specify by channel number.

Computation channel data*

101, etc.

Specify by channel number.

External input channel data*

201, etc.

Specify by channel number.

Constants

K01 to K60

Set to numeric values.

Communication input data

C01 to C60

Data set through communications.

Status of remote control*
input

D01 to D08**

The value is 1 when remote control input is
ON and 0 when it is OFF.

Pulse input*

P01 to P08

Counts the number of pulses per scan interval.

Q01 to Q08**

Counts the number of pulses per second.

Internal switch status

S01 to S30

1 or 0.

Alarm output relay* status

I01 to I36

The value is 1 when activated and 0 when
deactivated.

Flag

F01 to F08

1 or 0. Set the flag using the event action
function (for details, see section 1.7).

* This is an option.

** Values such as 01 are terminal numbers.

The table below shows the data that can be used with TLOG, CLOG, and PRE.

Checked data is usable.

Data

Math Func.

Meas.
CH

Comp.
CH

Ext.
input CH

Constant Comm.

Input

Remote Pulse Internal

Switch

Relay Flag

TLOG

CLOG

PRE

Other Functions

For example, TLOG.SUM(S01), CLOG.AVE(001.002.K01), and PRE(S01) are not allowed.

• Order of Operation

Computation functions are performed every scan interval, starting with the smallest

channel number.

Example: If you specify 102 = 101 + 103, the value of the previous scan interval is

used for the 103 value.

• How Computation Functions Handle Units

In computations, measured values are handled as values without units. For example,

if the measured data from channel 001 is 20 mV and the measured data from channel
002 is 20 V, the computed result of 001 + 002 is 40.

• How Computed Data Is Displayed

You can set a span for the computed data displayed on each computation

channel. Computation channels can be displayed on all operation screens, just like
measurement channels.

For configuration instructions, see section 10.3.

• Alarms

You can set a maximum of four different alarms on each computation channel. The

alarm types are high limit alarm (H), low limit alarm (L), delay high limit alarm (T), and
delay low limit alarm (t).

• How Computed Data Is Saved

Just as with measured data, computation channel computed data can be saved as

display data, event data, manually sampled data, and report data.

• Computation Data Dropout

A computation data dropout occurs if a mathematical operation is not completed within

the scan interval.

• The computation icon in the status display section turns yellow.
• When a computation data dropout occurs, the computed data of the scan interval in

which the dropout occurred is set to the same value as the data immediately before
the dropout.

• If computation data dropout occurs frequently, reduce the load on the CPU by

reducing the number of computation channels or by setting a longer scan interval.

For operating instructions, see section 10.4.

1.9 Computation and Report Functions (/M1 and /PM1 options)