Report Function

This function is used to create hourly, daily, weekly, and monthly reports.

For configuration instructions, see section 10.5.

• Report Data Types

You can select four of the following types of report data: maximum value, minimum

value, average value, sum value, and instantaneous value.

• Report Types

Type

Description

Hourly report

Produces report data for the previous one hour every hour on the hour.

Daily

Produces report data for the previous day every day at a specified time.

Weekly report

Produces report data for the previous week every week at a specified time on
a specified day of the week.

Monthly report

Produces report data for the previous month at a specified day and time.

• Combinations of Reports That Can Be Produced

The MV can produce hourly reports, daily reports, hourly and daily reports, daily and

weekly reports, and daily and monthly reports.

• Source Channels

You can select the source channels from measurement channels, computation

channels, and external input channels. Report data is not produced for channels that
are set to Skip or Off.

Model

Number of Report Channels

RD-MV1004, RD-MV1008, RD-MV2008

12

RD-MV1006, RD-MV1012, RD-MV1024

24

RD-MV2010, RD-MV2020, RD-MV2030, RD-MV2040,
RD-MV2048

60

• Units in Sum Operations

With sum operations, data is summed over the scan interval. However, for flow rate

values and other values whose units are time based (/s, /min, /h, or /day), a simple
summation results in the actual value not matching the computed result, because
the scan interval and the time unit of the input value are different. In such cases, set
the sum unit, (the Sum scale parameter in the MV interface), to match the unit of the
input value so that a sum with the same unit as the input value is calculated.

For example, if the scan interval is 2 s, and the input value is 100 m

3

/min, a simple

summation would add 100 every 2 s resulting in 3000 after one minute. However, if
the sum unit is set to /min, then 2 s/60 s is multiplied every scan interval before the
value is added giving a result that has the right time based (m

3

/min) unit.

The following conversion equations are used to compute the sum. The scan interval

unit is seconds.

Off: Σ(the measured data at every scan interval)
/s:

Σ(the measured data at every scan interval) × the scan interval

/min: Σ(the measured data at every scan interval) × the scan interval/60
/h:

Σ(the measured data at every scan interval) × the scan interval/3600

/day: Σ(the measured data at every scan interval) × the scan interval/86400

• Displaying Report Data

You can display report data by using key operations.

For configuration instructions, see sections 5.5 and 5.6.

• Saving Report Data

See section 1.5.

• Report Data Values

The range of displayable values for report data, ignoring the decimal point, is

–9999999 to 99999999 (except –3.4×10

38

to 3.4×10

38

for sum values).

For special cases and exceptions, see “Special Data Handling Cases and

Exceptions” in this section.

For details on the report file format, see appendix 3.