App index • errors related to ftp client – Yokogawa Button Operated MV2000 User Manual

Page 246

Advertising
background image

12-7

M-4660

Troubleshooting and Maintenance

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

• Errors Related to FTP Client

For a description of the FTP client function of the MV, see the Communication Interface
User’s Manual (IM RD-MV1000-17E)
. The detail code does not appear in the error
message on the screen. You can view the code on the FTP log display of the MV or using
the FTP log output via communications.

Code

Message

280

IP address is not set or FTP function is not available.

Further details are provided by the character string that appears after error code 280.
Character String and Details
HOSTADDR

An IP address has not been assigned to the MV.
Check the IP address.

DORMANT

Internal processing error.

1

LINK

Data link is disconnected.
Check the cable connection.

281

FTP mail box operation error.

Further details are provided by the character string that appears after error code 281.
Character String and Details
MAIL

Internal processing error.

1

STATUS

Internal processing error.

1

TIMEOUT

Internal processing error.

1

PRIORITY

Internal processing error.

1

NVRAM

Internal processing error.

1

282

FTP control connection error.

Further details are provided by the character string that appears after error code 282.
Character String and Details
HOSTNAME

Failed the DNS lookup (search the IP address corresponding to the host name).

Check the DNS setting and the destination host name.

TCPIP

Internal processing error.

1

UNREACH

Failed to connect to a control connection server.

Check the address setting and that the server is running.

OOBINLINE

Internal processing error.

1

NAME

Internal processing error.

1

CTRL

The control connection does not exist.
Check that the server does not drop the connection and that it responds within the proper

time period.

IAC

Failed to respond in the TELNET sequence.
Check that the server does not drop the connection and that it responds within the proper

time period.

ECHO

Failed to transmit data on the control connection.
Check that the server does not drop the connection and that it responds within the proper

time period.

REPLY

Failed to receive data on the control connection.
Check that the server does not drop the connection and that it responds within the proper

time period.