Index, Pretrigger function – Yokogawa DAQWORX User Manual

Page 15

Advertising
background image

1-9

IM WX13-01E

Before Using the

AddT

rigger Software

1.1 Overview of Functions

1

2

3

4

5

Index

6

Example: when the start condition is to scan for 2 alarms and the stop

condition is to scan for 1 alarms (OR condition).

Logging stops at the point stop condition alarm 1 occurs. At that point (B) the start

conditions are being met (alarm 1 or 2 is occurring) but logging does not start. The

start condition’s alarm 1 is cleared and reactivated between points B and C’, but

logging does not start because start condition’s alarm 2 is still occurring during that

time, and the start condition continues to be met. Both start condition alarms are
cleared for the first time at point C, making the start conditions no longer met. Logging
finally starts thereafter at point D, when the start condition is met again. (See the
following figure for the letters referred to in the text above.)

Start

Condition

Time

Stop

Condition

Alarm 1

Alarm 1
Alarm 2

Logging period

Logging period

Logging stops

Period during which alarms are occurring

Logging starts

C

C’

B

D

A

Pretrigger Function

If the start condition is an alarm trigger or level trigger, you can use a pretrigger function.

The pretrigger function allows you to save only the specified number of data prior to the

trigger start point. The number of data specified does not include the trigger point itself.

The pretrigger function can be set in the range from 0 to 1799 data points. If you specify

0 data points, the pretrigger function is effectively disabled.

Number of Pretrigger Data Specified and the Recording Rate

When data is saved to a file, it is first thinned at the specified recording rate. The number

of data specified for the pretrigger represents the number of data after thinning. The

internal memory can save up to 1800 data acquired from the monitor server (see page

1-2, “AddTrigger Structure”). Because of this, the valid range for the data that can be

specified for the pretrigger varies depending on the recording rate. That range is from 0

to (1800 ÷ the recording rate) - 1.

For example, the recording rate in the figure below is 3, so the valid range is from 0 to

599.

Recording rate

Recording rate

Start trigger

1800 data