Condensate drain trap, Caution – Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 10

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

10

Before connecting piping to the unit, the water supply line

and return line must be flushed to eliminate the foreign

material. In low temperature applications, the water supply

line and return line should be insulated to prevent con-

densate and antifreeze solution should be used to protect

water-to-refrigerant heat exchanger from freezing damage.

See submittal drawings for water piping connection loca-

tion. The concentration of water/glycol solution depends

on the field application. On open loop systems, a water

strainer (16–20 mesh minimum, 20–40 mesh best) is rec-

ommended to be installed in the water inlet line to the unit

to eliminate contaminants and it must be used for units

having water-to-refrigerant brazed plate heat exchanger.

A water flow switch is recommended to be installed in line

to prevent possible freeze-up due to loss of water flow.

An air vent must be installed on the high side of the water

line to discharge the non-condensable air in order to avoid

unexpected high head pressure and poor cooling/heating

performance. Manual shut-off valves are recommended to

be installed for the convenience of future service.
A circuit balancing valve with pressure and temperature

gauge connections is recommended to be installed in the

water line for balancing and service.
See

Appendix K

for water line field mounted options and

accessories.

Water Source Heat Pump (WSHP) Water Piping and Connections

CAUTION

In areas where scaling can become serious, a periodic

cleaning for the water-to-refrigerant heat exchanger is

recommended. Standard water coil cleaning procedure

should be followed which must be done by a qualified ser-

vice mechanic.

Cooling coil drain pan is provided with a 1¼” MPT drain

connection. A drain trap and condensate line of equal size

must be field provided on the drain connection to prevent

air or sewer gases from being pulled into the unit caused

by the negative (suction) pressure and forcing water out of

the pan into the unit.
A label with recommended trap height is provided on the

unit as per Figure 3.

The trap height allows for the maximum suction pressure

after the cooling coil with intake damper, dirty pre and final

high efficiency filters, high efficiency heat wheel plus 1” w.c.

per ASHRAE guidelines for outdoor units with intake hood

or indoor unit with up to 0.5” w.c. external static intake duct.
Slope the drain lines downward in direction of flow 1/8 inch

per foot referring to local codes for proper drainage require-

ments. Installing a plug for cleaning of the trap is recom-

mended. Prime the trap by filling with water before start-up.

Winterize the drain line before freezing on outdoor units.
Check and clear drains annually at start of cooling sea-

son. Drainage problems can occur should drains be in-

active and dry out, or due to reduced water flow caused

by buildup of algae. Regular maintenance will prevent

these from occurring.

Condensate Drain Trap

6.0” [191 mm]

minimum

3.0” [76 mm]

minimum

PN 500005436

Condensate drain must be trapped as shown.

Refer to IOM for further instructions and maintenance.

Le drain de condensation doit être fabriqué et intallé tel que

le croquis ci-bas. Voir le manuel d’installation,

opération et maintenance pour instructions.

Unit baserail

Curb

Curb
support

6.578”

[167.08 mm]

3.375”

[85.73 mm]

Figure 3: Condensate drain trap label

Advertising