Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 44

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

44

10.66”

1.52”

9.56”

1.10”

2.01”

5.28”

0.21”

5.52”

5.15”

4.41”

AM..N4

9/10”...3/4” 3/8”...9/10” 9/10”...3/4”

4.88”

Figure K6: Outdoor three-way valve actuator (10 to 21 tons)

C

B

A

Figure K7: Actuator

Table K8: Outdoor Three-way Valve Actuator Technical

and Dimensional Data (10 to 21 tons)

Power supply

24 VAC ± 20% 50/60 Hz

24 VDC ± 10%

Power consumption

Running

Holding

2.5 W

0.4 W

Transformer sizing

5 VA (Class 2 power source)

Electrical connection

Screw termianl (for 26–14 GA wire)

½” conduit connector

Overload protection

Electronic throughout 0° to 95°

rotation

Operating range Y

2–10 VDC, 4–20 mA

Feedback output U

1–10 VDC, max. 0.5 mA

Input impedance

100Ω [0.1 mA], 500Ω

Angle of rotation

Max 95° adjustable with mechani-

cal stop

Torque

160 in-lb [16 Nm]

Direction of rotation

Reversible with switch

Position indication

Pointer

Manual override

External push button

Running time

95 seconds constant independent

of load

Humidity

5% to 95% RH non-condensing

(EN 60730-1)

Ambient temperature

−22°F to 122°F [−30°C to 50°C]

Storage temperature

−40°F to 176°F [−40°C to 80°C]

Housing IP66/67

UL Type 4X, NEMA 4X

Housing material

UL94-5VA

Agency listings†

cULus acc. to UL60730-1A/-2-

14,CAN/CSA E60730-1, CSA C22.2

No. 24-93, CE acc. to 89/336/EEC

Noise level

<45 db (A)

Servicing

Maintenance free

Quality standard

ISO 9001

Weight

3.3 lbs [1.5 kg]

† Rated impulse voltage 800V, type of action 1, control pollution degree 3

Table K9: Outdoor Three-way Valve Dimensions

(10 to 21 tons)

Value Nominal Size

Dimensions (Inches [mm])

Inches DN [mm]

A

B

C

1¼”

32 mm 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]

1½”

40 mm 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]

2”

50 mm 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]

Table K10: Actuator Specifications

Torque

162 in-lbs [18 Nm]

Angle of rotation

95° (adjustable with mechanical

stops)

Fits shaft diameter

9/16”...3/4”

Manual override

External push button

Direction of rotation

External switch

Dimensions

10.66” x 5.28” x 4.88”

[271 x 134 x 124 mm]

Electrical connection

Terminal strip

Overload connection

Electronic throughout rotation

Auxiliary switch(es)

Add on: 1 or 2 SPDT, 3A (0.5A

inductive) at 250V one switch

adjustable 25° to 85°

Housing specifications

NEMA 4/4X, IP66/IP67

Agency listings

cULus according to UL 30730-

1A/- 2-14, CAN/CSA E60730-

1:02, CE according to 2004/108/

EC and 2006/95/EC

Control shaft length

Minimum ¾”
Maximum 2¼”

Advertising