Smoke detector, Dirty filter sensor, Important – Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 29

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

29

Smoke Detector

Locate in a normally occupied area of premises. Recom-

mended for compliance to NFPA-90A and IMC Code 606.
VHCs can be equipped with a duct mount smoke detector

which will monitor the air when passing through the duct

system into the VHC. When sufficient smoke is detected,

an alarm condition is activated. By connecting the occupied

timer/sensor contacts to the NC alarm auxiliary contacts on

the duct sensor, an alarm condition will open the auxiliary

contact and stop operation of the VHC.

Dirty Filter Sensor

The VHCs can be equipped with dirty filter sensors which

monitor the pressure across the filters and close the con-

tacts when the filters become restricted with dirt. Field

wired connections can be made to the terminal interface for

both the supply and exhaust filter sensors.

301

302

410

411

24V 24V NC C

1 2 15 16

Figure F6: Smoke detector

301

302

304

305

305

306

307

308

320

321

322

323

324

325

326

327

328

329

DIRTY SUPPLY FILTER

24 VAC+ OUTPUTS

20 VA MAXIMUM

DIRTY EXHAUST FILTER

Figure F7: Dirty filter control

IMPORTANT

On DDC units, there is no dirty filter sensor output to con-

nect to. Rather, the dirty filter sensor is connected to the

DDC controller and will display a dirty filter alarm on the

BacStat II (user interface) when it senses the filter is dirty.

IMPORTANT

This wiring configuration cannot be used on DDC units

that are scheduled on/off through software.

Advertising