43

C

B

A

0.62” [16 mm]

2.99”

[76 mm]

1.0”

[25.5 mm]

5.28”

[134 mm]

9.76”

[248 mm]

9.21”

[234 mm]

Figure K4: Outdoor three-way valve actuator (6 to 8 tons)

C

3.46”

[88 mm]

8.5” [216 mm]

3.3”

[84 mm]

B

A

2.49”

[63.4 mm]

1.35”

[35 mm]

Figure K5: Indoor three-way valve actuator (10 to 21 tons)

Table K4: Outdoor Three-way Valve Actuator Technical

and Dimensional Data (6 to 8 tons)

Power supply

24 VAC ± 20% 50/60 Hz

24 VDC ± 10%

Power consumption

Running

Holding

2.5 W

0.4 W

Transformer sizing

5 VA (Class 2 power source)

Electrical connection

Screw terminal (for 26–14 GA wire)

Overload protection

Electronic throughout 0° to 95°

rotation

Operating range Y

2–10 VDC, 4–20 mA

Input impedance

600Ω

Angle of rotation

90° adjustable with mechanical stop

Direction of rotation

Reversible with switch

Position indication

Visual pointer

Manual override

External push button

Running time

95 seconds constant independent

of load

Humidity

100% RH

Ambient temperature

−22°F to 122°F [−30°C to 50°C]

Storage temperature

−40°F to 176°F [−40°C to 80°C]

Housing type

UL Type 4X/NEMA 4X/IP66 & IP67

Housing material

Polypropylene

Agency listings†

cULus acc. to UL60730-1A/-2-

14,CAN/CSA E60730-1, CSA C22.2

No. 24-93, CE acc. to 89/336/EEC

Quality standard

ISO 9001

† Rated impulse voltage 800V, type of action 1, control population

degree 3.

Table K5: Outdoor Three-way Valve Dimensions

(6 to 8 tons)

Value Nominal Size

Dimensions (Inches [mm])

Inches DN [mm]

A

B

C

1¼”

32 mm 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]

1½”

40 mm 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]

2”

50 mm 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]

Table K6: Indoor Three-way Valve Actuator Technical and

Dimensional Data (10 to 21 tons)

Power supply

24 VAC ± 20% 50/60 Hz

24 VDC ± 10%

Power consumption

Running

Holding

2.5 W

0.4 W

Transformer sizing

3 VA (Class 2 power source)

Electrical connection

½” conduit connector 18 GA ple-

num rated cable

_3 ft [1 m] _10 ft [3 m] _16 ft [5 m]

Overload protection

Electronic throughout 0° to 95°

rotation

Operating range Y

2–10 VDC, 4–20 mA

Feedback output U

1–10 VDC, max. 0.5 mA

Input impedance

100Ω [0.1 mA], 500Ω

Angle of rotation

90° adjustable with mechanical stop

Torque

180 in-lb [20 Nm]

Direction of rotation

Reversible with switch

Position indication

Handle

Manual override

External push button

Running time

95 seconds constant independent

of load

Humidity

5% to 95% RH non-condensing

(EN 60730-1)

Ambient temperature

−22°F to 122°F [−30°C to 50°C]

Storage temperature

−40°F to 176°F [−40°C to 80°C]

Housing

NEMA 2/IP54

Housing material

UL94-5VA

Agency listings†

cULus acc. to UL60730-1A/-2-

14,CAN/CSA E60730-1, CSA C22.2

No. 24-93, CE acc. to 89/336/EEC

Noise level

<45 db (A)

Quality standard

ISO 9001

† Rated impulse voltage 800V, control pollution degree 3, type of action1

(1.B for -S models)

Table K7: Indoor Three-way Valve Dimensions (10 to 21

tons)

Value Nominal Size

Dimensions (Inches [mm])

Inches DN [mm]

A

B

C

1¼”

32 mm 3.96” [100.6] 2.21” [56.2] 2.14” [54.3]

1½”

40 mm 4.39” [111.6] 2.45” [62.2] 2.33” [59.1]

2”

50 mm 4.90” [124.5] 2.68” [68.0] 2.60” [66.0]

Advertising