Enthalpy wheel pressure drop vs. flow formula, Table l1: enthalpy wheel pressure drop coefficient – Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 47

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

47

Appendix L: Enthalpy Wheel Pressure Drop vs. Flow Formulae and

Curves

Enthalpy Wheel Pressure Drop vs. Flow

Formula

Flow in cfm = pressure drop measured in ” w.c. / pressure

drop coefficient based on enthalpy wheel size

Enthalpy Wheel Pressure Drop vs. cfm

Curves (based on wheel diameter x depth

(inches))

Table L1: Enthalpy Wheel Pressure Drop Coefficient

Enthalpy Wheel Size

(diameter x depth in inches)

Pressure Drop

Coefficient

36 x 4

0.00029551

36 x 6

0.00032675

36 x 8

0.00038283

42 x 4

0.00021504

42 x 6

0.00023397

42 x 8

0.00027220

50 x 4

0.00014783

50 x 6

0.00016034

50 x 8

0.00018639

0.5

0.6

0.7

0.8

0.9

1.0

0.4

0.3

0.1

0.2

0.0

0

500

1,000

1,500

2,000

2,500

3,000

Airflow [cfm]

Pr

essur

e Dr

op [in. w

.g.]

36” x 8” (High)

36”x 6” (Standard)

36” x 4” (Medium)

Figure L1: Pressure drop – 36” enthalpy wheel diameter

0.5

0.6

0.7

0.8

0.9

1.0

0.4

0.3

0.1

0.2

0.0

0

500

1,000

1,500

2,000

2,500

3,000

3,500

4,000

Airflow [cfm]

Pr

essur

e Dr

op [in. w

.g.]

42” x 8” (High)

42”x 6” (Standard)

42” x 4” (Medium)

Figure L2: Pressure drop – 42” enthalpy wheel diameter

0.5

0.6

0.7

0.8

0.9

1.1

1.0

0.4

0.3

0.1

0.2

0.0

0

1,000

2,000

3,000

5,000

6,000

4,000

Airflow [cfm]

Pr

essur

e Dr

op [in. w

.g.]

50” x 8” (High)

50”x 6” (Standard)

50” x 4” (Medium)

Figure L3: Pressure drop – 50” enthalpy wheel diameter

Advertising