Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 42

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

42

C

B

A

0.62” [16 mm]

2.99”

[76 mm]

1.0”

[25.5 mm]

5.28”

[134 mm]

9.76”

[248 mm]

9.21”

[234 mm]

Figure K2: Outdoor three-way valve actuator (2 to 5 tons)

Table K6: Outdoor Three-way Valve Actuator Technical

and Dimensional Data (2 to 5 tons)

Control

2–10 VDC, 4–20 mA

Power supply

24 VAC ± 20% 50/60 Hz

24 VDC ± 10%

Power consumption

Running

Holding

2.5 W

0.4 W

Transformer sizing

5 VA (Class 2 power source)

Electrical connection

Screw terminal (for 26–14 GA wire)

Overload protection

Electronic throughout 0° to 95° rotation

Input impedance

100 kΩ [0.1 mA], 500Ω

Angle of rotation

90°, adjustable with mechanical stop

Direction of rotation

Reversible with switch

Position indication

Visual pointer

Manual override

External push button

Running time

95 seconds constant independent

of load

Humidity

100% RH

Ambient temperature

−22°F to 122°F [−30°C to 50°C]

Storage temperature

−40°F to 176°F [−40°C to 80°C]

Housing type

UL Type 4X/NEMA 4X/IP66 and

IP67

Housing material

Polypropylene

Agency listings

cULus acc. to UL 60730-1A/- 2-14,

CAN/CSA E60730-1, CSA C22.2

No. 24-93, CE acc. to 89/336/EEC

Quality standard

ISO 9001

C

2.6”

[66 mm]

2.34”

[59.4 mm]

7.97” [200 mm]

A

B

1.69”

[42 mm]

3.22”

[82 mm]

Figure K3: Indoor three-way valve actuator (6 to 8 tons)

Table K1: Outdoor Three-way Valve Dimensions (2 to 5 tons)

Value Nominal Size

Dimensions (Inches [mm])

Inches DN [mm]

A

B

C

½”

15 mm 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]

½”

15 mm 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]

¾”

20 mm 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]

1”

25 mm 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]

Table K2: Indoor Three-way Valve Actuator Technical and

Dimensional Data (6 to 8 tons)

Power supply

24 VAC ± 20% 50/60 Hz

24 VDC ± 10%

Power consumption

Running

Holding

1.5 W

0.4 W

Transformer sizing

3 VA (Class 2 power source)

Electrical connection

½” conduit connector 18 GA, ple-

num rated cable 3 feet [1 m]

_3 ft [1 m] _10 ft [3 m] _16 ft [5 m]

Overload protection

Electronic throughout 0° to 95°

rotation

Operating range Y

2–10 VDC, 4–20 mA

Feedback output U

1–10 VDC, max. 0.5 mA

Input impedance

100Ω [0.1 mA], 500Ω

Angle of rotation

90° adjustable with mechanical stop

Direction of rotation

Reversible with protected switch

Position of indication

Handle

Manual override

External push button

Running time

Constant independent of load

LRB24-SR

95 seconds

LRX24-SR

_150 sec. _95 sec. _60 sec.

_45 sec. _35 sec.

Humidity

5% to 95% RH non-condensing (EN

60760-1)

Ambient temperature

−22°F to 122°F [−30°C to 50°C]

Storage temperature

−40°F to 176°F [−40°C to 80°C]

Housing

NEMA 2/IP54

Housing material

UL94-5VA

Agency listings

cULus acc. to UL60730-1A/-2- 14,

CAN/CSA E60730-1, CSA C22.2

No. 24-93, CE acc. to 9/336/EEC

Noise level

<35 db (A)

Quality standard

ISO 9001

Electrical connection

Screw terminal (for 26–14 GA wire)

protected (NEMA 2/IP20)

Table K3: Indoor Three-way Valve Dimensions (6 to 8 tons)

Value Nominal Size

Dimensions (Inches [mm])

Inches DN [mm]

A

B

C

½”

15 mm 2.41” [61.1] 1.39” [35.2] 1.20” [30.6]

½”

15 mm 2.38” [60.4] 1.72” [43.7] 1.26” [32.1]

¾”

20 mm 2.73” [69.3] 1.81” [45.9] 1.45” [36.8]

1”

25 mm 3.09” [78.4] 1.81” [45.9] 1.56” [39.8]

Advertising