Appendix E: Electrical Data

Electric Preheat and Post Heat Calculation

FLA = W / (1.73 x voltage)

Electric Preheaters and Post Heaters

Electric preheaters and post heaters are available in:

• Single-point or two-point power connection

• Two-stage, four-stage* or SCR control

• 1 kW increments for all three-phase voltages.

Electric Heater Performance Calculations

Temperature Rise (°F) = kW x 3,160

cfm

kW = cfm x temperature rise (°F)

3,160

Electric single point preheaters and post heaters have the

following limitations:

• 208 VAC – 24 kW maximum

• 230 VAC – 27 kW maximum

• 460 VAC – 67 kW maximium

• 575 VAC – 84 kW maximum

IMPORTANT

Electric preheaters and post heaters range from 1 to 120

kW (see below for heater limitations) and actual FLA values

of individual heaters will vary based upon the size, tem-

perature rise and voltage. Consult the factory for actual FLA

values. All electric heaters require three-phase voltage.

IMPORTANT

Four-stage electric post heaters are only available with

kW ratings higher than 10 kW.

CAUTION

All electrical installations and wiring require correct wire

gauge sizing and protection according to local building codes.

WARNING

All units equipped with two-point electric post heaters

require two-point power connections, one to the control

panel and one to the electric heater fed from a field sup-

plied single disconnect.

!

Table E1: Full Load Amperage (FLA)

HP

Voltage

208/1/60

230/1/60

208/3/60

230/3/60

460/3/60

575/3/60

Blower Motor

0.5

4.5

4.0

1.8

2.2

1.1

0.9

0.75

5.4

6.0

2.7

2.7

1.4

1.1

1.0

6.8

7.0

3.4

3.4

1.7

1.4

1.5

10.2

10.2

5.0

5.0

2.5

2.0

2.0

14.0

14.0

6.4

6.0

3.0

2.4

3.0

17.8

17.0

10.6

10.6

4.8

3.4

5.0

22.0

22.0

15.3

12.8

6.4

5.1

7.5

32.0

32.0

25.0

19.2

9.6

7.8

10.0

29.3

26.8

13.4

10.3

Wheel Drive Motor and Controls

2.4

2.2

2.4

2.2

1.1

0.9

The blower motor FLA values show in in the above table are for one motor only.

Table E2: Electric Preheater and Post Heater Limitations

VAC VHC-36 up to

50 kW

VHC-42 up to

70 kW

VHC-50 up to

120 kW

208

24

24

24

50

70

120

230

27

27

27

50

70

120

460

50

70

67

50

70

120

575

50

70

84

50

70

120

Shaded areas – single-point post heater limitations

White areas – two-point post heater limitations