Appendix f: terminal control diagrams – Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 27

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

27

Occupied Ventilation

Occupied ventilation is achieved by closing the occupancy

contact to the terminal interface shown in Figure F1. These

terminals require a dry contact which could be provided by

a number of types of controls such as a timer, light sensor,

occupancy sensor, Building Management System or other.

The unit will not operate unless these contacts are closed.

Occupied Timer Sensor

Occupied ventilation is achieved by connection to the

terminal interface shown in Figure F2. These terminals re-

quire a dry contact which could be provided by a number of

types of controls such as a timer, light sensor, occupancy

sensor, Building Management System, or other. The unit

will not operate unless these contacts are closed.

Unoccupied Recirculation

Supply fan recirculation for heating and cooling can be

achieved by connecting dry contact controls to the terminal

interface provided in the control panel area. This terminal

requires a dry contact closure from a field provided and

wired device.

Appendix F: Terminal Control Diagrams

301

302

304

305

305

306

307

308

320

321

322

323

324

325

374

375

376

377

OCCUPANCY

CONTACT

CR

Note: This is the only

connection needed to

start single-speed units.

Figure F1: Occupied ventilation for DDC controls package

and electro-mechanical controls (EMC)

301

302

304

305

305

306

307

308

320

321

322

323

324

325

326

327

328

329

1

2 3 4 5

12

6

9

Figure F2: Occupied ventilation for DDC controls package

and electro-mechanical controls (EMC)

301

302

304

305

305

306

307

308

320

321

322

323

324

325

326

327

328

329

UNOCCUPIED RECIRCULATION

CONTACT (OPTIONAL)

CR

Figure 10: Unoccupied recirculation for DDC controls units

IMPORTANT

DDC units can be turned on/off through software.

Advertising