Electrical connections – Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 8

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

8

Power Supply

Units are available in all voltages and phases. Please see

Appendix E

for electrical data. These units may or may not

have a factory installed disconnect switch. If disconnect is

field supplied, provide a disconnect as per local electrical

codes and NEC. Use copper conductors only.
All field wiring must comply with NEC and local require-

ments. In Canada, electrical connections must be in accor-

dance with CSA C22.1 Canadian Electrical Code Part One.
Units equipped with electric preheaters and/or post heaters

have either single-point or two-point power connections.

See

Appendix E

, submittal data and/or nameplate to de-

termine which. All units equipped with two-point electric

heaters require two-point power connection—one to the

unit control panel and one to the electric heater fed from a

single field supplied disconnect.

Field Connection

A high voltage connection hole is located on the outside of

the unit with knock-out; see submittal drawings for location.

A field installed disconnect switch must use a liquid-tight

connector between the disconnect switch and the outside

panel of the unit eliminating any water penetration into the

control box. A wiring diagram is located within the control

panel area of the unit.
A low voltage Field Wiring (FW) interface is provided near

the control Panel (PNL) terminals for shipped loose or field

supplied controls, sensors or interlock connections. The

location of the field wiring and panel terminals may vary

depending upon options selected as illustrated in Figure 2.

The low voltage field wiring entry is made through the side

of the unit below the input power supply connection (see

Appendix G

) which runs through the outside casing and

requires a liquid-tight connector or conduit to avoid water

penetration.
Installer must provide wiring for controls that are supplied

optionally and shipped loose or field supplied. All field sup-

plied low voltage wiring must be Class 2. Mark the Field

Wiring terminals schematic (

Appendix G

) with the con-

nections completed and leave with the unit for start-up and

service.

Units will require a start contact interlock from a remote

time clock, light sensor, occupancy sensor, manual selec-

tor switch or remotely through BACnet from a Building

Management System (BMS) depending on ventilation

control scheduling mode required. Select required inter-

lock and ventilation control scheduling mode from descrip-

tion below.
See

Appendix F

and

Appendix G

for wiring terminal con-

trol diagram examples and standard Field Wiring (FW) ter-

minal and interlock connections available.

Units Supplied with DDC Control Package

The DDC control package enables stand alone opera-

tion of the VHC unit and includes a factory installed, pro-

grammed and run tested stand alone microprocessor

based controller, all necessary sensors and interfaces to

provide control of optional post conditioning functions. See

the VHC-36, 42 and 50 DDC Control Package Manual

(VCES-DDC-IOM-1 (500020459)) for overview, installation

and start-up.
An intelligent programmable interface device (BacStat II)

with built in room sensor is included for communication,

display, setpoint control and to allow for servicing and is

shipped loose for field wiring and installation at the unit or

remotely. Determine required location for installation and

connect using two twisted pair cables, the first for power

connection. The LinkNet cable needs to be balanced 100

to 120 ohm nominal impedance twisted shielded pair cable,

nominal capacitance of 16 PF/FT or lower.

Units Supplied with an Electro-mechanical

Controls (EMC) Package

The EMC controls package or dry contact control option

include: all relays, motor starters, motor overloads, damper

actuators, heating and cooling initiate contacts and se-

lected option pickup points. All necessary connections are

wired to a terminal strip in the control panel for field wiring

connections to a Building Management System (BMS), for

field supplied DDC or standard controls and thermostats.

See the Control Contractor’s flow and wiring schematics

for connection details.

Ventilation Control Scheduling Modes

Occupied Ventilation (Ov)

If the occupancy contact closes or a jumper is placed

across terminals FW 304–305 this will enable the unit to

run in 100% fresh air mode. Free cooling and defrost will

initiate based on the setpoint.

Unoccupied Recirculation (Ur)

If the unoccupied recirculation contact closes or a jumper

is placed across terminals FW 305–306 the unit will turn off

unless there is a call for heating/cooling or dehumidification

across the heating/cooling or dehumidification contacts.

Electrical Connections

WARNING

When installed, the appliance must be electrically

grounded in accordance with local codes or, in the ab-

sence of local codes, with the National Electrical Code,

ANSI/NFPA70, and/or the Canadian Electrical Code CSA

C22.1. Unit cabinet must have an uninterrupted, unbroken

electrical ground to minimize the possibility of personal

injury if an electrical fault should occur. Failure to follow

this warning could result in the Installer being liable for

personal injury of others.

!

Advertising