Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 38

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

38

sure the heater is properly interlocked to prevent it from

being energized before the damper is fully open.

3 – Operating Electric Coil Heaters

3.1 Minimum Airflow

Ensure that sufficient airflow as marked on the name-

plate is passing through the heater. Airflow should be

evenly distributed across the entire face of the heater.

Use air turning vane at duct elbows and splitter damper

at duct branch-offs to streamline the airflow in the heater.

Use suitable airflow sensing device or interlock the

heater with fan. An insufficient airflow will lead to the

opening of the auto-reset thermal cut-out or damage to

the heating elements.

3.2 Warning

The air flowing through the duct where the heater is in-

stalled shall not contain any combustible particles, nor any

flammable vapor or gas.

3.3 Air Temperature

The air temperature should not exceed 120°F [49°C] at the

heater outlet.

3.4 Minimum Static Pressure and Air Direction

The heater is protected by a differential pressure switch.

To keep the contact of this switch closed, it is necessary to

maintain a minimum total pressure of 0.07” of water for a

constant flow.

3.5 Manual Reset Thermal Cut-out

This protection device is standard on all heaters of less

than 300 volt and 30 kW and is optional on all other heat-

ers. Please check the auto-reset thermal cut-out before re-

setting the manual thermal cut-out. If any defect has been

detected in the auto-reset thermal cut-out, it will be neces-

sary to replace it before resetting the manual reset thermal

cut-out.

4 – Maintenance

All electric coil heaters have been designed to operate long

term without problems. Those responsible for equipment

and maintenance should be aware of the following sugges-

tions.

4.1 Visual Inspection

It is strongly recommended to complete a periodic inspec-

tion. This precautionary step will help to keep your instal-

lations operating well. Note these eventual first signs of

problems:

• Accumulation of dust on the heating elements.

• Signs of overheating on the heater frame.

• Traces of water or rust on the control box.

4.2 Electrical Inspection

Two weeks after start-up, all electric connections to

contactors should be checked and tightened up. Before

each heating season, check the resistance between the

heating elements and ground. It is also recommended

to check the electrical connections to heating elements,

magnetic contactors and main power lugs. This inspection

is recommended monthly during the first four months of

operation. After that, two inspections per heating season

are sufficient.

4.3 Checkpoints

• Check all fuses.

• Check the resistance to ground for each circuit.

• Check the resistance phase-to-phase for each circuit.

• Check the tightening of connections at all contactors

and heating elements.

• Check all contactors.

4.4 Off-season Maintenance

Where tubular heating elements are used, it is strongly rec-

ommended that you start the heating system from time to

time. This precaution will prevent moisture from percolating

through the terminal gaskets into the heating element and

accumulating in the insulating powder. Should a heater be

shut off for a long period, we recommend that you check

carefully the resistance to ground for each circuit. It is im-

portant not to power a heater when too low a resistance

to ground has been measured. It is also recommended to

pay attention to any other heater operating in normal condi-

tions. Control components such as step controllers or mod-

ulating valves (SCR) should be maintained and checked

according to respective Manufacturer’s instructions. Any

defective components should be replaced only with identi-

cal original parts.

Advertising