Water Flow Switch

Flow Switch Dimensions

Flow Switch Installation

The flow switch must be externally field mounted in the

leaving or outlet water line. Before installation, the flow

switch vane must be trimmed for the size of piping being

used. A full size, trimmable stainless steel vane is provided

with a removable laminate template. This template is cali-

brated for brass or ductile iron reducing tee and forged

steel straight tee/brushing combination which allows for

field installation in pipeline from ½” to 2” diameter. See

Table K11 for approximate actuation and deactivation val-

ues.

1. Carefully unpack the flow switch and remove any

packing material from the lower housing. Trim the

vane at the appropriate mark for the size of piping

being used.

2. Apply thread tape or sealant to the ½” male NPT

mounting threads and install the flow switch in the sys-

tem piping with the arrow on the side pointing in the

direction of flow.

3. The flow switch must be field wired to the standard

field wiring (FW) terminal strip as per wiring schematic

for 24 VAC.

4. Avoid exceeding any of the maximum electrical ratings

which can lead to failure.

5. After installation, set the switch action to normally

open or normally closed. To change the switching

from normally open to normally closed, loosen, but

do not remove the two screws on the top cap. Slide

the reed switch assembly to expose the switch ac-

tion selected. Tighten screws when adjustment is

complete.

1

1

2

2

3

3

4

4

5

5

One screw attaches
actuator to valve

Four actuator mounting
positions

Two-way flow pattern

Three-way flow pattern
(mixing shown)
Top of valve stem indicates
direction of flow
(Flow A to AB shown)

Note: For diverting flow, flow
enters in AB and diverts
to A and B ports.

CCW

CCW

4 x 90°

A

A

AB

AB

B

A-AB = 100%

A-AB = 100%
B-AB = 0%

Figure K14: Valve and actuator assembly and installation

WARNING

Mechanical shock or vibration can cause permanent

damage to the switch. Avoid dropping the unit on hard

surfaces.

!

Figure K15: Valve and actuator assembly and installation

2¼” [57 mm]

1” [25 mm]

¼ (6) travel to
normally closed
position

(2) 22 AWG Leadwires
18 (460) long

1/8 NPT – switch shown
in normally open position

Lower body

7/8 hex

½ NPTM

Vane

2-7/16” [62 mm]

2-7/8” [73 mm]

Table K11: Flow Switch Performance Data Table

Cold Water Flow Rates –

Approximate Actuation/Deactuation

Pipe

Trim

NO

NC

½”

L

2.6/2.3

2.6/2.5

9.8/8.7

9.8/9.5

¾”

J

3.1/2.7

3.1/2.8

11.7/10.2

11.7/10.6

1”

H

4.8/4.5

4.8/4.4

18.2/17.0

18.2/16.7

1¼”

E

6.2/5.6

6.1/5.6

23.5/21.2

23.1/21.2

1½”

C

8.2/7.7

8.2/7.7

31.0/29.1

31.0/29.1

2”

Full

9.5/9.1

9.5/9.0

36.0/34.4

36.0/34.1

GPM upper, LPM lower