Freeze protection – Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 40

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

40

NEMA 4x rated actuator must be installed. The hydronic

valves are intended for use in a normal indoor/outdoor en-

vironment for hot or cold water or glycol solutions to 60%

concentration with a medium temperature rating of 0°F to

212°F [−18°C to 100°C]. The actuator must be field wired

to the standard field wiring (FW) terminals #435, 436 and

437 depending on valve size. The valve and actuator are

preassembled for 0% flow to the coil when the unit does

not require heating or cooling.
See Table K3 for two-way valve sizing, performance data

and dimensions; installation and technical data is included

with accessory parts. See the wiring schematic for connec-

tion information.

Freeze Protection

A water flow switch and a temperature sensor as an op-

tion and mounted on the water return or leaving side of the

condenser are used to monitor the presence or absence

of flow and the water temperature which will shut down

the compressor and unit for freeze protection. The flow

switch also features an adjustment which allows the user

to change the switch from normally open (NO) to normally

closed (NC).
The temperature sensor is factory mounted and wired in-

ternally. The flow switch must be externally field mounted

in the leaving or return water line and field wired to the

standard field wiring (FW) terminal strip as per wiring sche-

matic. See performance, dimensions and installation data

at the end of this appendix.

Table K2: Three-way Valve Sizing and Performance Data

Tons

Minimum US

GPM

Condenser Pressure

Drop (PSI)

Condenser

Maximum

Pressure (PSI)

Three-way Head Pressure Control Valve
C

v

Maximum Pressure

(PSI)*

Size FPT

2

6

4.3

400

3.0

600

½

3

9

9.2

400

3.0

600

½

4

12

3.0

400

4.7

600

¾

5

15

5.0

400

7.4

600

¾

6

18

7.0

400

7.4

600

1

8

24

7.7

400

7.4

600

1

10

30

4.3

400

10.0

400

12

36

7.0

100

19.0

400

14

42

6.0

400

19.0

400

*Maximum close off pressure 200 psi.

Table K3: Two-way Valve Sizing and Performance Data

Tons

Minimum US

GPM

Condenser Pressure

Drop (PSI)

Condenser

Maximum

Pressure (PSI)

Two-way Water Shut-off Valve

C

v

Maximum Pressure

(PSI)*

Size FPT

2

6

4.3

400

24

600

¾

3

9

9.2

400

24

600

¾

4

12

3.0

400

24

600

¾

5

15

5.0

400

24

600

¾

6

18

7.0

400

19

400

8

24

7.7

400

19

400

10

30

4.3

400

19

400

12

36

7.0

100

37

400

*Maximum close off pressure 200 psi.