MAMM-VHC-IOM-1A (JANUARY 2013)

7

Open access doors or panels and remove all packaging

from the unit. Note that there is packaging for wheel sup-

port during shipping. Removal of all packaging is critical.

Internal Packaging

Refer to Table 1 for the effect of undersized equivalent duct

diameter.

Calculate Equivalent Duct Diameter

The equivalent duct diameter of the fan outlet.
= (4ab + n)

0.5

= (4 x 13.5 x 9.5)

0.5

n

= 12.75

= ~13
So the straight duct length required would be:
= 2.5 x 13

= 32.5” long [2.7 feet]

Intake and exhaust hoods for these models are shipped

separately from the unit. To install hoods see

Appendix B

.

A quick connect for the damper motors is provided to con-

nect to the main body of the unit. Make sure that all screws

are secured to maintain proper support and keep seals

water-tight.

Handles for lift off exterior access panels with screw door

fasteners are provided but must be installed on site. Han-

dles and fasteners are secured inside the unit.

Hood Installation

Access Panels

IMPORTANT

Securing door fasteners too tightly has negative effects on

the door gasket and should be avoided.

Table 1: Effect of Undersized Equivalent Duct Diameter

Pressure

recovery

No Duct

12%

Effective

Duct

25%

Effective

Duct

50%

Effective

Duct

100%

Effective

Duct

0%

50%

80%

90%

100%