Airflow balancing – Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 14

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

14

For proper performance the unit must operate and be

balanced at the design supply and exhaust airflow rates.

Permanent or temporarily field supplied and installed flow

measuring stations (FMS) can be used to measure airflow

or by using other ASHRAE suggested methods. Where

space is limited in the outdoor air or exhaust air ducts

for measurements, pressure drop readings can be taken

across the enthalpy wheel rotor and airflow extrapolated

from the curves in

Appendix L

for the wheel effectiveness

category or thickness. Heat recovery performance is tested

in accordance to AHRI Standard 1060 and is accurate to

within +/− 5% if there is no dirt buildup in the heat recovery

wheel rotor.
When FMS are used it is important to locate it in the “warm

side” ductwork to minimize the effects of differences in air

density especially during cold outside conditions. Air den-

sity variations can affect the FMS by more than 15%. The

FMS should be located downstream from straight sections

of duct and not immediately after fans or obstructions that

will cause turbulent flow.
Imbalanced airflow may cause supply air temperatures

to be below freezing. Adequate freeze protection such as

glycol or low limit temperature protection for downstream

coils or reheat to protect building systems must be field

provided.

Setting Flow Rate

Units supplied with belt driven double width double inlet

fans have an adjustable motor sheave factory set at the

midpoint of travel at rpm for the flow rate and external static

specified. With optional VFD driven motors this factory set-

ting is at 60 Hz. For 100% outdoor and exhaust, flow rate

should be balanced with motors operating at high speed

and at 60 Hz by adjusting the motor sheave pitch diameter.

The VFD can be used for fine tuning depending on se-

quence.
With the optional direct driven plenum supply fan the VFD

is used for speed setting and balancing at the required

Hertz.
With the optional internal bypass the airflow rate may be

reduced. Consult the factory for setting the flow rate during

internal bypass.

WARNING

Disconnect the main power switch to the unit before per-

forming service and maintenance procedures.

!

IMPORTANT

On initial power up, the unit will perform a system check

and operate at high speed for five seconds.

Airflow Balancing

Advertising