Mammoth 800 to 5500 CFM: Dedicated Outdoor Air System with Enthalpy Wheels (VHC) User Manual

Page 12

Advertising
background image

MAMM-VHC-IOM-1A (JANUARY 2013)

12

Free Cooling

Power connected, unit ventilating, free cooling call. Wheel

stops rotating.

Variable Speed Setpoint Free Cooling

Power connected, unit ventilating. Wheel modulates to

keep discharge temperature air at setpoint.

Unit Fault

An external unit fault can be initiated by removing the

dry contact jumper to the field wire terminal in the control

panel. This contact is normally closed and requires an

open contact to initiate a fault and shut down the unit.

Dirty Filter Sensor

The VHCs can be equipped with dirty filter sensors which

monitor the pressure across the filters and close the con-

tacts when the filters become restricted with dirt. Field

wired connections can be made to the terminal interface

for both the supply and exhaust filter sensors (electro-me-

chanical controls [EMC] units only).

Remote Fan Control

Remote fan control can be achieved by connecting dry

contacts to the terminal interface (during occupied or un-

occupied recirculation). These controls could also be the

following: SPDT switch, dehumidistat, CO2 sensor, light sen-

sor, heat sensor, timer, Building Management System, etc.

CO

2

Ventilation Control

VHCs can be directly controlled by a CO

2

controller (acces-

sory or field supplied) that can be connected to the supply

and exhaust high speed contact terminals (VFD units only).

As the CO

2

levels exceed acceptable limits, dry contacts

close raising high speed fan ventilation. See Appendix F,

CO

2

Ventilation Control

. Alternatively a field supplied CO

2

controller output can be connected to the BMS which can

then be connected to the supply and exhaust fan modu-

lating signal input terminals (VFD units only). As the CO

2

placed across terminals, heat wheel stops,

defrost recirculation damper opens, outside

and exhaust air dampers (if equipped) begin to

close and supply blower starts.

c. Occupied recirculation (Or) (DDC control pack-

age only): With the occupied recirculation

contact closed or a jumper placed across termi-

nals, heat wheel starts (not in free cooling), de-

frost recirculation damper closes (if equipped),

outside air damper (if equipped) opens. After

outside air damper opens supply blower starts,

exhaust air damper (if equipped) opens; after

exhaust air damper opens, exhaust blower

starts, occupied recirculation damper opens,

outside and exhaust air dampers modulate to

the damper minimum setpoints.

5. Check that dampers are operating properly.

6. Check that blowers and heat wheel are rotating in the

correct direction.

7. For occupied recirculation scheduling mode the out-

side air and exhaust air dampers must be adjusted

during start-up to achieve the required outside and ex-

haust air volumes. See

Airflow Balancing

for further

information.

8. Re-check the voltage at the disconnect switch against

the nameplate and against phase-to-phase read-

ings on three-phase with all blowers operating. If the

voltage is not within 10% of rated or 2% of phase-to-

phase have the condition corrected before continuing

start-up.

9. Check amperage draw to each motor on each

phase against motor nameplate FLA. If significantly

different, check ductwork static and/or take correc-

tive action.

10. Before activating the compressor on WSHP units, are

water shut-off valves open and is water circulating

through the water-to-refrigerant heat exchanger.

11. Enable cooling and check if the sound of the compres-

sor is normal or if there is excessive vibration.

12. Check all field and factory refrigerant and water piping

connections for leaks and correct.

13. Enable heating options, see start-up and check out in-

structions in

Appendix J

for electric coil and complete.

14. Check the operation of the control options provided

on the unit. A functional description is provided below

and in the VHC-36, 42 and 50 DDC Control Package

Manual.

15. Check the setpoints on the DDC Points Reference,

adjust and record changes as required.

16. When unit has achieved steady state take measure-

ments and complete the readings section of the start-

up report in

Appendix H

and send copy of the start-up

report to Mammoth to validate warranty. Maintain a

copy of the report at the unit for future reference.

Optional Controls and Accessory Sequence and Interlocks

Advertising