NORD Drivesystems BU0280 User Manual

Page 22

Advertising
background image

Supplementary Manual DeviceNet for NORDAC SK 200E

22

Subject to technical amendments

BU 0280 GB

Control connection details

Terminal/
Designation

Function
[factory setting]

Data

Description / wiring suggestion

Parameter

44 24V

External 24V supply

24VDC ±20%
≈ 50mA , reverse polarity
protected

External supply voltage of the
technology unit and supply of the
digital inputs (DIN1 and DIN2)

-

40 GND

Reference potential
for digital signals

-

C1 DIN1

Digital input 1
[I/O DeviceNet DIN1]

Low 0V ... 5V
High 15V ... 30V
R

i

= 8.1k

Input capacitance 10nF
Scan rate 1 ms
Inputs as per EN 61131-2
Type 1

Each digital input has a reaction
time of 1ms.

P174

C2 DIN2

Digital input 2
[I/O DeviceNet DIN2]

P174

77 Sys

+

System bus

data cable +

System bus interface

-

78 Sys

-

System bus

data cable -

-

40 GND

Reference potential
for digital signals

-

Potential isolation

45 24V

24V supply
bus potential

-

75 DVN

+

DeviceNet Bus +

DeviceNet

The use of twisted, shielded two-
conductor cable is urgently
recommended

-

76 DVN

-

DeviceNet Bus -

-

46 GND

Bus

Data ground

Bus reference potential

-

90 SHLD

Shield

Data cable shield

-

45 +24V

Bus

Electrically isolated
24V bus supply

24VDC +/-20%
≤ 50mA reverse polarity
protected

The external supply voltage of the
technology unit is at the potential of
the DeviceNet bus.

-

75 DVN

+

DeviceNet Bus +

DeviceNet

The use of twisted, shielded two-
conductor cable is urgently
recommended

-

76 DVN

-

DeviceNet Bus -

-

46 GND

Bus

Data ground

Bus reference potential

-

Advertising