NORD Drivesystems BU0280 User Manual

Page 24

Advertising
background image

Supplementary Manual DeviceNet for NORDAC SK 200E

24

Subject to technical amendments

BU 0280 GB

Control connection details

Terminal/

Designation

Function
[factory setting]

Data

Description / wiring suggestion

Parameter

1 24V Bus

2

External 24V supply 24VDC -/+20%

≤ 50 mA , reverse polarity
protected

Voltage supply at DeviceNet bus
potential

-

3 DVN

+

4

DeviceNet Bus +

DeviceNet

The use of twisted, shielded two-
conductor cable is urgently
recommended

-

5 DVN

-

6

DeviceNet Bus -

-

7 GND

BUS


8

Data ground bus

Voltage supply at DeviceNet bus
potential

-

9 SHLD

Bus shield

-

10 PE

Earthing

-

Potential isolation

11 24V

12

13

External 24V supply

24VDC -/+20%
≤ 50mA , reverse polarity
protected

External supply voltage for system
bus and digital inputs (DIN1 to
DIN4)

-

14 Sys

+

System bus

data cable +

System bus interface

-

15 GND

Reference potential
for digital signals

External supply voltage for system
bus and digital inputs (DIN1 to
DIN4)

-

16 Sys

-

System bus

data cable -

System bus interface

-

17 GND

18

Reference potential
for digital signals

External supply voltage for system
bus and digital inputs (DIN1 to
DIN4)

-

19 DIN1

Digital input 1
[I/O DeviceNet DIN1]

Low 0V ... 5V
High 15V ... 30V
R

i

= 8.1k

Input capacitance 10nF

Scan rate 1 ms
Inputs as per EN 61131-2
Type 1

Each digital input has a reaction
time of 1ms.

P174

20 DIN3

Digital input 3
[I/O DeviceNet DIN3]

P174

21 GND

22

Reference potential
for digital signals

External supply voltage for system
bus and digital inputs (DIN1 to
DIN4)

-

23 24V

24

External 24V supply

As for terminal 11

-

Advertising