NORD Drivesystems BU0280 User Manual

Page 52

Advertising
background image

Supplementary Manual DeviceNet for NORDAC SK 200E

52

Subject to technical amendments

BU 0280 GB

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P546

[-01]

...

[-03]

Function Bus setpoint 1 ... 3

S

P

0 ... 24

{ [-01] = 01 }

{ [-02] = 00 }

{ [-03] = 00 }

In this parameter, a function is allocated to the output setpoint during bus actuation.

NOTE:

For further details, please refer to the description for P400.

[-01] = Bus setpoint value 1

… [-02] = Bus setpoint value 2

(only for PPO Type 2 or 4)

… [-03] = Bus setpoint value 3

(only for PPO Type 2 or 4)

Possible values which can be set:

0 =

Off

1 =

Setpoint frequency (16 bit)

2 =

Frequency addition

3 =

Frequency subtraction

4 =

Minimum frequency

5 =

Maximum frequency

6 =

PI process controller actual value

7 =

PI process controller setpoint

8 =

Actual frequency PID

9 =

Actual PID frequency limited

10 =

Actual PID frequency monitored

11 =

Limiting torque current

12 =

Torque current switch-off limit

13 =

Limiting current

14 =

Current switch-off limit

15 =

Ramp time

16 =

Lead torque (P214) multiplication

17 =

Servo mode torque

18 =

Curve travel calculator

19 =

Digital In bits 0...7

20 =

...24 reserved for Posicon