4 Commissioning

BU 0280 GB

Subject to technical amendments

45

4.3.7

Class 42 – AC- Drive Object

Attr.

Access

Name

Type

Description

3

Get

AtReference

BOOL

Actual value corresponds to the setpoint

4

Get/Set

NetRef

BOOL

Setpoints sent via DeviceNet are enabled.

6 Get DriveMode USINT

This parameter is always 0 (specific to vendor). The drive
mode can be obtained via FI parameter P509.

7

Get

SpeedActual

INT

Actual speed in rpm.

8

Get/Set

SpeedRef

INT

Setpoint speed in rpm.

9

Get

CurrentActual

INT

Actual current in the motor phases, resolution in 0.1A

15

Get

PowerActual

INT

Current power, 0.01kW

16

Get

InputVoltage

INT

Input voltage of the FI in V

17

Get

OutputVoltage

INT

Output voltage of the FI in V

18 Get/Set

AccelTime UINT Run-up time for the speed ramp in ms from 0 rpm to

HighSpdLimit

19 Get/Set

DecelTime UINT Braking time for the speed ramp in ms from LowSpdLimit

to 0 rpm.

20 Get/Set

LowSpdLimit UINT Minimum possible speed in rpm

21 Get/Set

HighSpdLimit UINT Maximum possible speed in rpm

29

Get

RefFromNet

BOOL

Status of setpoint enabling via DeviceNet
0 = Setpoint via DeviceNet disabled
1 = Setpoint via DeviceNet enabled

In Class 42, Instances 1 to 4 are supported, whereby the value of the instance is addressed to the relevant FI
on the system bus. E.g. FI 2 on the system bus is accessed via Instance 2.

4.3.8

Class 43 – Acknowledge Handler Object

Inst.

Attr.

Access

Name

Type

Description

1 1 Get/Set

Acknowledge
Timer

UINT

Time before the Acknowledge signal is
sent
Range from 1ms to 65535ms
Resolution = 1ms

1 2 Get/Set

Retry

Limit

USINT

Number of Acknowledge timeouts at
which a RetryLimit_Reached event is
executed

1 3 Get COS Producing

Connection
instance

UINT

Connection Instance contains the path
of the I/O application object which
receives information from the Ack
Handler.