NORD Drivesystems BU0280 User Manual

Page 42

Advertising
background image

Supplementary Manual DeviceNet for NORDAC SK 200E

42

Subject to technical amendments

BU 0280 GB

1 7 Get Baud Rate Switch

Changed

BOOL

TRUE = If there has been a change to the baud
rate switches since the last reset or power up.

1 8 Get MAC ID Switch

Value

USINT Current ID setting on the DIP switch

1 9 Get Baud Rate

Switch Value

USINT Current baud rate setting on the DIP switch

4.3.3

Class 4 – Assembly Object

Inst.

Attr.

Access

Type

Description

20 3 Get/Set

STRUCT

4 Byte

Write AC drive profile 1 to FI

21 3 Get/Set

STRUCT

4 Byte

Write AC drive profile 2 to FI

70 3 Get

STRUCT

4 Byte

Read AC drive profile 1 from FI

71 3 Get

STRUCT

4 Byte

Read AC drive profile 2 from FI

100 3

Get/Set STRUCT

5 Byte

Describe NORD AC profile 1 to FI

101 3

Get/Set STRUCT

8 Byte

Describe NORD AC profile 2 to FI

102 3

Get/Set STRUCT

33 Byte

Describe NORD AC profile 3 to FI

110 3

Get

STRUCT

5 Byte

Read out NORD AC profile 1 from FI

111 3

Get

STRUCT

8 Byte

Read out NORD AC profile 2 from FI

112 3

Get

STRUCT

33 Byte

Read out NORD AC profile 3 from FI

120 3

Get/Set STRUCT

1 to 33 Byte

Describe variables of NORD AC profile 1 to FI

130 3

Get

STRUCT

1 to 33 Byte

Read out variables of NORD AC profile 1 from FI

The instances 70, 71, 110, 111, 112 and 130 are only updated if I/O messages are received.
Transmission to instances 20, 70, 100, 101, 102 & 120 is only meaningful if no I/O messages are sent,
as otherwise these would overwrite the contents of the explicit response message. Reading and
writing can only be carried out for the active instance.

.